02.00
Fault
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
F018
Short circuit or overloading of binary outputs
(active in all operating states)
Possible fault causes
Short circuit or overload at terminals 46, 48, 50 or 52 and 26 or 34
Fault value:
1
Short circuit or overload at binary outputs
NOTE
This monitoring function is deactivated in the delivery state. It can be activated via parameter P820.

10.1.2.3 External faults

F019
Fault message from free function block FB286
(active in all operating states)
Fault value:
1
the binector wired via parameter U100 Index.005 is in the state log."1"
2
the binector wired via parameter U100 Index.006 is in the state log."1"
3
the binector wired via parameter U100 Index.007 is in the state log."1"
4
the binector wired via parameter U100 Index.008 is in the state log."1"
F020
Fault message from free function block FB287
(active in all operating states)
Fault value:
1
the binector wired via parameter U101 Index.005 is in the state log."1"
2
the binector wired via parameter U101 Index.006 is in the state log."1"
3
the binector wired via parameter U101 Index.007 is in the state log."1"
4
the binector wired via parameter U101 Index.008 is in the state log."1"
F021
External fault 1
(active in all operating states)
Bit 15 in control word 1 was in the log. "0" state for longer than the time set in P360 index 001
F022
External fault 2
(active in all operating states)
Bit 26 in control word 2 was in the log. "0" state for longer than the time set in P360 index 002
F023
Fault message from free function block FB2
(active in all operating states)
Fault value:
1
the binector wired via parameter U100 Index.001 is in the state log."1"
2
the binector wired via parameter U100 Index.002 is in the state log."1"
3
the binector wired via parameter U100 Index.003 is in the state log."1"
4
the binector wired via parameter U100 Index.004 is in the state log."1"
F024
Fault message from free function block FB3
(active in all operating states)
Fault value:
1
the binector wired via parameter U101 Index.001 is in the state log."1"
2
the binector wired via parameter U101 Index.002 is in the state log."1"
3
the binector wired via parameter U101 Index.003 is in the state log."1"
4
the binector wired via parameter U101 Index.004 is in the state log."1"
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
Description
Further information (r047.002 to r047.016)
r047 Index 002 to 016:
i002 Bit 8 = 1:
Overload at terminal 46
Bit 9 = 1:
Overload at terminal 48
Bit 10 = 1: Overload at terminal 50
Bit 11 = 1: Overload at terminal 52
Bit 12 = 1: Overload at terminal 26 (24 V output)
Bit 13 = 1: Overload at terminal 34, 44 and/or 210
(24 V output)
Faults / Alarms
10-7