11.50 Activation of fault messages and alarm messages
Only active with optional technology software S00
U100
Source for the activation of F023 and F019
(2100)
Selection of the binectors that activate fault messages F023 or F019 on log.
*
"1"
S00
0 = Binector B0000
1 = Binector B0001
etc.
Up to SW 1.7: F023 (without fault value) if binector = 1 (FB 2)
SW 1.8 and later:
i001:
F023 with fault value 1 (FB 2)
i002:
F023 with fault value 2
i003:
F023 with fault value 3
i004:
F023 with fault value 4
i005:
F019 with fault value 1 (FB 286)
i006:
F019 with fault value 2
i007:
F019 with fault value 3
i008:
F019 with fault value 4
U101
Source for the activation of F024 and F020
(2101)
Selection of the binectors that activate fault messages F024 or F020 on log.
*
"1"
S00
0 = Binector B0000
1 = Binector B0001
etc.
Up to SW 1.7: F024 (without fault value) if binector = 1 (FB 3)
SW 1.8 and later:
i001:
F024 with fault value 1 (FB 3)
i002:
F024 with fault value 2
i003:
F024 with fault value 3
i004:
F024 with fault value 4
i005:
F020 with fault value 1 (FB 287)
i006:
F020 with fault value 2
i007:
F020 with fault value 3
i008:
F020 with fault value 4
U102
Source for the activation of F033 and F053
(2102)
Selection of the binectors that activate fault messages F033 or F053 on log.
*
"1"
S00
0 = Binector B0000
1 = Binector B0001
etc.
Up to SW 1.7: F033 (without fault value) if binector = 1 (FB 4)
SW 1.8 and later:
i001:
F033 with fault value 1 (FB 4)
i002:
F033 with fault value 2
i003:
F033 with fault value 3
i004:
F033 with fault value 4
i005:
F053 with fault value 1 (FB 288)
i006:
F053 with fault value 2
i007:
F053 with fault value 3
i008:
F053 with fault value 4
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
Value range
[Unit]
Steps
All binector numbers
FB 2, FB 286
1
FB 3, FB 287
All binector numbers
1
FB 4, FB 288
All binector numbers
1
Parameter list
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind:
P052 = 3
None
P051 = 40
[up to
off-line
SW1.7]
8
[SW 1.8 and
later]
FS=0
Type: L2
Ind:
P052 = 3
None
P051 = 40
[up to
off-line
SW1.7]
8
[SW 1.8 and
later]
FS=0
Type: L2
Ind:
P052 = 3
None
P051 = 40
[up to
off-line
SW1.7]
8
[SW 1.8 and
later]
FS=0
Type: L2
11-85