11.14 Ramp-function generator
(see also Section 8, Sheet G136 and Section 9)
See P639 and P640 for ramp-function generator setting parameters
Limitation at ramp-function generator output (setpoint limiting))
The effective limitations are:
Upper limit:
Minimum value of P300 and the four connectors selected with P632
Lower limit:
Maximum value of P301 and the four connectors selected with P633
Note:
The limiting values for both the positive and negative setpoint limits can have a positive or negative sign. The negative setpoint
limit, for example, can therefore be parameterized to a positive value and the positive setpoint limit to a negative value.
P300
Positive limitation at ramp-function generator output
FDS
P301
Negative limitation at ramp-function generator output
FDS
P302
Select ramp-function generator / ramp-up integrator mode
*
0
Normal ramp-function generator operation
FDS
Ramp-function generator setting 1 (P303 to P306) is applied.
When a binary selectable input parameterized as "Ramp-
function generator setting 2" (P307 to P310)" (selected in P637)
or "Ramp-function generator setting 3" (P311 to P314)"
(selected in P638), generator setting 2 or 3 is applied as
appropriate.
1
Ramp-up integrator operation: When the setpoint is reached for
the first time, ramp-function generator setting 1 is switched over
to a ramp-up/down times = 0
2
Ramp-up integrator operation: When the setpoint is reached for
the first time, ramp-function generator setting 1 is switched over
to generator setting 2 (P307 to P310)
3
Ramp-up integrator operation: When the setpoint is reached for
the first time, ramp-function generator setting 1 is switched over
to generator setting 3 (P311 to P314)
Ramp-function generator parameter set 1
P303
Ramp-up time 1
FDS
P304
Ramp-down time 1
FDS
P305
Lower transition rounding 1
FDS
P306
Upper transition rounding 1
FDS
Ramp-function generator parameter set 2
Ramp-function generator parameter set 2 is selected via the binector parameterized in P637.
P307
Ramp-up time 2
FDS
P308
Ramp-down time 2
FDS
P309
Lower transition rounding 2
FDS
P310
Upper transition rounding 2
FDS
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
Value range
No. indices
[Unit]
Factory
Steps
setting
Type
-200.00 to 199.99
Ind: 4
[%]
FS=100.00
0.01%
Type: I2
-200.00 to 199.99
Ind: 4
[%]
FS=-100.00
0.01%
Type: I2
0 to 3
Ind: 4
1
FS=0
Type: O2
0.00 to 650.00
Ind: 4
[s]
FS=10.00
0.01s
Type: O2
0.00 to 650.00
Ind: 4
[s]
FS=10.00
0.01s
Type: O2
0.00 to 100.00
Ind: 4
[s]
FS=0.00
0.01s
Type: O2
0.00 to 100.00
Ind: 4
[s]
FS=0.00
0.01s
Type: O2
0.00 to 650.00
Ind: 4
[s]
FS=10.00
0.01s
Type: O2
0.00 to 650.00
Ind: 4
[s]
FS=10.00
0.01s
Type: O2
0.00 to 100.00
Ind: 4
[s]
FS=0.00
0.01s
Type: O2
0.00 to 100.00
Ind: 4
[s]
FS=0.00
0.01s
Type: O2
Parameter list
See
Change
(Access /
Status)
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
11-33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents