Siemens SIMOREG DC Master 6RA7028-6DS22 Operating Instructions Manual page 453

Microprocessor-based converters from 6kw to 1900kw for variable-speed dc drives 6ra70 series
Table of Contents

Advertisement

02.00
PNU
Description
P696
Source for selection of "Stop speed controller I component" function
*
Selection of binector to control the "Stop I component" function
BDS
0 = binector B0000
1 = binector B0001
etc.
When the binector selected in P696 changes to the log. "1" state, the I
component of the speed controller is stopped.
P697
Source for selection of enabling of dv/dt injection
*
Selection of binector to control enabling of dv/dt injection (state "1" =
BDS
enable)
0 = binector B0000
1 = binector B0001
etc.
P698
Source for selection of enabling command for speed controller PI / P
*
function switchover
BDS
Selection of binector to control enabling of the PI / P controller switchover
function (see also P222)
0 = binector B0000
1 = binector B0001
etc.
11.35 Analog inputs (main actual value, main setpoint, selectable inputs)
(see also Section 8, Sheets G113 and G114)
Analog input terminals 4 / 5 (main setpoint)
P700
Signal type of "Main setpoint" analog input
*
0 = Voltage input 0 to ±10 V
1 = Current input 0 to 20 mA
2 = Current input 4 to 20 mA
P701
Normalization of "Main setpoint" analog input
This parameter specifies the percentage value which is generated for an
FDS
input voltage of 10V (or an input current of 20mA) at the analog input.
The following generally applies:
For voltage input:
[%] =
P
701
10
With current input:
[%] =
P
701
20
mA
P702
Offset for "Main setpoint" analog input
P703
Mode of signal injection at "Main setpoint" analog input
*
0 = Injection of signal with sign
1 = Injection of absolute value of signal
2 = Injection of signal with sign, inverted
3 = Injection of absolute value of signal, inverted
P704
Source for selection of sign reversal at "Main setpoint" analog input
*
Selection of binector to control sign reversal at the analog input ("1" state
= reverse sign)
0 = binector B0000
1 = binector B0001
etc.
P705
Filtering time for "Main setpoint" analog input
Note: Hardware filtering of approximately 1 ms is applied as standard.
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
Y
V
X .. Input voltage in volts
X
Y .. % value which is generated for input
voltage X
Y
X .. Input current in mA
X
Y .. % value which is generated for input
current X
Value range
No. indices
[Unit]
Factory
Steps
setting
Type
All binector numbers
Ind: 2
1
FS=0
Type: L2
All binector numbers
Ind: 2
1
FS=1
Type: L2
All binector numbers
Ind: 2
1
FS=0
Type: L2
0 to 2
Ind: None
1
FS=0
Type: O2
-1000.0 to 1000.0
Ind: 4
[%]
FS=100.0
0.1%
Type: I2
-200.00 to 199.99
Ind: None
[%]
FS=0.00
0.01%
Type: I2
0 to 3
Ind: None
1
FS=0
Type: O2
All binector numbers
Ind: None
1
FS=0
Type: L2
0 to 10000
Ind: None
[ms]
FS=0
1ms
Type: O2
Parameter list
See
Change
(Access /
Status)
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Online
11-61