Electronics power supply
Terminal type: Type 49 plug-in terminal
Function
Connec-
tion
Incoming supply
400V
or
Incoming supply
230V
NOTE
In the case of line voltages which exceed the tolerance range specified in Section 3.4, the
electronics supply voltage, field circuit mains supply connection and converter fan connection
must be adjusted by means of transformers to the permissible value stated in Section 3.4. It is
essential to use an isolating transformer for rated line voltages in excess of 460V.
The rated supply voltage for the armature circuit (index 001) and the field circuit (index 002) must
be set in parameter P078.
Fan
(for forced-cooled converters ≥ 400A)
Terminal type: DFK-PC4 plug-in terminal (screw-type)
The insulation on the supply cables must be taken up to the terminal housing.
Function
Incoming supply 400V bis 460V
PE conductor
or
Incoming supply 230V
WARNING
The converter might overheat if the incorrect phase sequence is connected (incorrect direction
of rotation of fan).
Check:
• On converters up to 850A (fan at bottom), check whether fan is rotating in direction of arrow
• On converters of > 850A (fan at top), check whether fan is rotating in counter-clockwise
direction (to left) when viewed from above
Caution: Rotating parts can cause physical injuries!
Siemens AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
Maximum cross-section 1.5mm
Terminal
XP
1
5U1
2
5W1
NC
3
5N1
1
5U1
2
5W1
3
5N1
Maximum connection cross-section 4mm
Terminal
4U1
4V1
4W1
4U1
4N1
2
, finely stranded
Connection values/Remarks
2AC 380 to 460 (+15% / – 25%); I
(– 35% for 1min)
Internal fuse protection with F1, F2 on board C98043-A7002
or -A7003
external fuse protection 6A, characteristic C recommended
1AC 190 (– 25%) to 230 (+15%); I
(– 35% for 1min)
Internal fuse protection with F1, F2 on board C98043-A7002
or -A7003
external fuse protection 6A, characteristic C recommended
2
, finely stranded
Connection values/Remarks
3AC 400 to 460
For further details, see technical data in Section 3.4
1AC 230
For further details, see technical data in Section 3.4
Connections
=1A
n
=2A
n
6-55