Siemens SIMOREG DC Master 6RA7028-6DS22 Operating Instructions Manual page 166

Microprocessor-based converters from 6kw to 1900kw for variable-speed dc drives 6ra70 series
Table of Contents

Advertisement

Start-Up
Fault code
106
107
108
Rules for job/response processing:
A job or a response can only ever refer to one parameter.
The master must send the job repeatedly until it receives an appropriate response from the
slave. The master recognizes the response to the job it has sent by analysing the response
identifier, the parameter number, the parameter index and the parameter value.
The complete job must be sent in one telegram. The same applies to the response.
The actual values in repeats of response telegrams are always up-to-date values.
If no information needs to be fetched via the PKW interface (but only PZD) in cyclic
operation, then a "No job" job must be issued.
PROFIBUS devices have a variety of difference performance features. In order to ensure that all
master systems can correctly address each supplementary board, the characteristic features of
each board are stored in a separate device master file (GSD).
File SIEM8022.GSD is needed for the CB1 and file SIEM8045.GSD for the CBP.
The appropriate file can be chosen in the selection menu for the SIMOVERT MASTER DRIVES
files in later versions of the configuring tool.
If a device master file is not available in the menu, it can be collected from an Internet site. The
Internet address is http://www.ad.siemens.de/support/html_76/index.shtml.
Product Support/PROFIBUS GSD files/Drives/ . Have all entries displayed using the search function
and click on the search results.
SIMOVERT/SIMOREG/SIMADYN CBP
File: siem8045.gsd
The communication boards can only be operated on a non-Siemens master as a DP standard
slave, the corresponding GSD file containing all necessary information for this mode.
Detailed information about communication via PROFIBUS can be found in Section 8.2 of the
compendium for SIMOVERT MASTER DRIVES Motion Control (order no. 6SE7080-0QX50). The
description in this document is fully applicable in every respect, except that the specified parameter
numbers differ from those used on the SIMOREG DC MASTER 6RA70.
As a start-up support tool, the PROFIBUS board supplies data which can be displayed in n732.001
to n732.032 (1
The values of the indices are as follows:
Index
001/033 Status_1 (CBP_Status)
Meaning of bits as for CBP
7-24
Job not implemented in drive
Text cannot be written (changed)
Incorrect number of parameter values
st
CB) or n732.033 to n732.064 (2
Meaning for CB1
Meaning
With job "Write all indices"
nd
CB).
Meaning for CBP/CBP2
CBP_Status
Bit0: "CBP Init", CBP is being initialized or waiting to
be initialized by the basic unit
(not set in normal operation)
Bit1: "CBP Online", CBP is selected by basic unit
(set in normal operation)
Bit2: "CBP Offline", CBP not selected by basic unit
(not set in normal operation)
Bit3: Illegal bus address (P918)
(not set in normal operation)
Bit4: Diagnostic mode activated (U711 <> 0)
(not set in normal operation)
Bit8: Incorrect identifier bytes transferred (incorrect
configuring message from PROFIBUS Master)
(not set in normal operation)
Bit9: Incorrect PPO type (incorrect configuring
message from PROFIBUS Master)
(not set in normal operation)
Bit10:Correct configuring data received from
PROFIBUS_DP Master (set in normal
operation)
SIMOREG DC Master
02.00
SIEMENS AG
6RX1700-0AD76
Operating Instructions