Parameter list
PNU
Description
U807
Telegram failure time on paralleling interface
(2807)
0
0.001...65.000 Permissible time interval between two data exchange
Fault message F014 is displayed if no data are exchanged with the parallel-
connected converter within this delay period.
The monitoring function is implemented within a 20 ms cycle. For this
reason, only setting values which constitute a multiple of 20 ms are
meaningful.
Note:
The telegram monitoring function is active
from the receipt of the first error-free telegram after connection of the
electronics power supply
from the receipt of the first error-free telegram after the telegram
monitor has responded (i.e. monitoring timeout).
U808
Source for triggering of message F014
(2808)
Selection of binector which must trigger message F014 when it switches to
*
log. "1"
6040 = binector B6040
6041 = binector B6041
n809
Diagnostic information for paralleling interface
(2809)
i001 to i008=Free-running counter, overflow at 65535
i001:
Error-free Telegram Counter
i002:
Errored Telegram Counter
i003:
Transmit Error Counter
i004:
Receive Error Counter
i005:
Phase Error Counter
i006:
Baud rate Error Counter
i007:
Bad BCC Counter
i008:
Timeout Counter
i009:
Bit 2: Valid telegram received from (if master) / for (if slave)
...
Bit6: Valid telegram received from (if master) / for (if slave)
n810
Display of active slaves
(2810)
For master: Display of responding slaves
For slave:
Display of slave addresses to which master is sending valid
telegrams
11-140
No time monitoring
operations before a fault message is output.
address 2
address 6
6
5
4
3
2
1
0
Value range
No. indices
[Unit]
Factory
Steps
setting
Type
0.000 to 65.000
Ind: None
[s]
FS=0.100
0.001s
Type: O2
6040, 6041
Ind: None
FS=6040
Type: L2
0 to 65535
Ind: 9
Type: O2
Ind: None
Type: V2
SIEMENS AG
SIMOREG DC Master
Operating Instructions
02.00
See
Change
(Access /
Status)
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Offline
P052 ≥ 0
P052 = 3
6RX1700-0AD76