Siemens SIMOREG DC Master 6RA7028-6DS22 Operating Instructions Manual page 441

Microprocessor-based converters from 6kw to 1900kw for variable-speed dc drives 6ra70 series
Table of Contents

Advertisement

02.00
PNU
Description
P554
Source for the Influencing quantity of the Tn-adaptation
*
FDS
Selection of which connector is connected at the influencing quantity for
adaptation of the n controllers integration time
0 = connector K0000
1 = connector K0001
etc.
P555
Source for the Influencing quantity of the droop adaptation
*
FDS
Selection of which connector is connected at the influencing quantity for
adaptation of the n controllers droop
0 = Connector K0000
1 = Connector K0001
etc.
P556
Adaptation n controller P gain: Threshold 1
FDS
P557
Adaptation n controller integration time: Threshold 1 [SW 1.7 and later] 0.00 to 100.00
FDS
P558
Adaptation n controller droop: Threshold 1
FDS
P559
Adaptation n controller P gain: Threshold 2
FDS
P560
Adaptation n controller integration time: Threshold 2 [SW 1.7 and later] 0.00 to 100.00
FDS
P561
Adaptation n controller droop: Threshold 2
FDS
Speed controller - speed droop limitation
P562
Positive speed droop limitation
FDS
P563
Negative speed droop limitation
FDS
11.30 Field reversal
(see also Section 9)
P580
Source for selection of "Direction of rotation reversal using field
*
reversal"
BDS
Selection of binector to control the "Direction of rotation reversal using field
reversal" function
0 = binector B0000
1 = binector B0001
etc.
P581
Source for selection of "Braking with field reversal"
*
Selection of binector to control the "Braking with field reversal" function
BDS
0 = binector B0000
1 = binector B0001
etc.
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
Value range
[Unit]
Steps
All connector
[SW 1.7 and later]
numbers
1
All connector
numbers
[SW 1.7 and later]
1
0.00 to 100.00
[%]
0.01%
[%]
0.01%
[SW 1.7 and later] 0.00 to 100.00
[%]
0.01%
0.00 to 100.00
[%]
0.01%
[%]
0.01%
[SW 1.7 and later] 0.00 to 100.00
[%]
0.01%
0.00 to 199.99
[%]
0.01%
-199.99 to 0.00
[%]
0.01%
All binector numbers
1
All binector numbers
1
Parameter list
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: 4
P052 = 3
FS=0
P051 = 40
Type: L2
off-line
Ind: 4
P052 = 3
FS=0
P051 = 40
Type: L2
off-line
Ind: 4
P052 = 3
FS=0.00
P051 = 40
Type: O2
on-line
Ind: 4
P052 = 3
FS=0.00
P051 = 40
Type: O2
on-line
Ind: 4
P052 = 3
FS=0.00
P051 = 40
Type: O2
on-line
Ind: 4
P052 = 3
FS=0.00
P051 = 40
Type: O2
on-line
Ind: 4
P052 = 3
FS=0.00
P051 = 40
Type: O2
on-line
Ind: 4
P052 = 3
FS=0.00
P051 = 40
Type: O2
on-line
Ind: 4
P052 = 3
FS=100.00
P051 = 40
Type: O2
Online
Ind: 4
P052 = 3
FS=-100.00
P051 = 40
Type: I2
Online
Ind: 2
P052 = 3
FS=0
P051 = 40
Type: L2
Offline
Ind: 2
P052 = 3
FS=0
P051 = 40
Type: L2
Offline
11-49

Hide quick links:

Advertisement

Table of Contents