Parameter list
PNU
Description
U759
Source for selection of sign reversal at
analog inputs on EB1
(2759)
Selection of binector to control sign reversal at the analog input ("1" state
*
= reverse sign)
0 = binector B0000
1 = binector B0001
etc.
i001: AI1 of the first EB1
i002: AI2 of the first EB1
i003: AI3 of the first EB1
i004: AI1 of the second EB1
i005: AI2 of the second EB1
i006: AI3 of the second EB1
U760
Filtering time for analog inputs on EB1
(2760)
Note: Hardware filtering of approximately 0.2 ms is applied as standard
*
i001: AI1 of the first EB1
i002: AI2 of the first EB1
i003: AI3 of the first EB1
i004: AI1 of the second EB1
i005: AI2 of the second EB1
i006: AI3 of the second EB1
U761
Source for enabling of analog inputs on EB1
(2761)
Selection of binector to control enabling of the analog input ("1" state =
enabled)
*
0 = binector B0000
1 = binector B0001
etc.
i001: AI1 of the first EB1
i002: AI2 of the first EB1
i003: AI3 of the first EB1
i004: AI1 of the second EB1
i005: AI2 of the second EB1
i006: AI3 of the second EB1
n762
Display of analog inputs on EB1
(2762)
i001: AI1 of the first EB1
i002: AI2 of the first EB1
i003: AI3 of the first EB1
i004: AI1 of the second EB1
i005: AI2 of the second EB1
i006: AI3 of the second EB1
U763
Source for output value at analog outputs on EB1 [SW 1.5 and later]
(2763)
Selection of connector whose value must be output at the analog output
*
0 = connector K0000
1 = connector K0001
etc.
i001: AO1 of the first EB1
i002: AO2 of the first EB1
i003: AO1 of the second EB1
i004: AO2 of the second EB1
U764
Mode of signal injection at analog outputs on EB1 [SW 1.5 and later]
(2764)
0 = Injection of signal with sign
1 = Injection of absolute value of signal
*
2 = Injection of signal with sign, inverted
3 = Injection of absolute value of signal, inverted
i001: AO1 of the first EB1
i002: AO2 of the first EB1
i003: AO1 of the second EB1
i004: AO2 of the second EB1
11-134
Value range
[Unit]
Steps
All binector numbers
[SW 1.5 and later]
1
0 to 10000
[SW 1.5 and later]
[ms]
1ms
[SW 1.5 and later]
All binector numbers
1
[SW 1.5 and later]
-200.0 to 199.99
[%]
0.01%
All connector
numbers
1
0 to 3
1
SIMOREG DC Master
02.00
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: 6
P052 = 3
FS=0
P051 = 40
Type: L2
Offline
Ind: 6
P052 = 3
FS=0
P051 = 40
Type: O2
Online
Ind: 6
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: 6
P052 = 3
Type: I2
Ind: 4
P052 = 3
FS=0
P051 = 40
Type: L2
Online
Ind: 4
P052 = 3
FS=0
P051 = 40
Type: O2
Online