02.00
Fault
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
F064
Watchdog timer has initiated a reset
(active in all operating states)
An internal microprocessor hardware counter monitors whether the program for calculating the firing pulses runs at least once
every 14 ms (program is executed on average every 2.7 to 3.3 ms). If this is not the case, the counter initiates a reset, Fo64 is
then displayed.
Possible fault causes
•
A7001 electronics board is defective
•
Excessive EMC-related interference is present (e.g. due to unprotected contactors, unscreened cables, loose shield
connections)
F065
Illegal microprocessor status
(active in all operating states)
An internal microprocessor hardware function monitors the microprocessor for illegal operating states.
Possible fault causes
•
A7001 electronics board is defective
•
Excessive EMC-related interference is present (e.g. due to unprotected contactors, unscreened cables, loose shield
connections)
F067
Converter cooling faulty
(active in operating states of ≤ o13)
The heatsink temperature monitoring function is activated 6s after connection of the electronics supply.
(The current heat sink temperature is indicated at parameter r013 and on connector K050)
Fault value:
1
Heatsink temperature > 95°C
2
Heatsink temperature sensor is defective
3
Converter fan is defective
F068
Analog measuring channel faulty (main setpoint, main actual value or analog select input)
(active in all operating states)
Hardware monitoring of measuring circuits
Possible fault causes
•
A7001 module defective
•
Measuring circuit saturated (input voltage at terminals 4 and 5 or 6 and 7 higher than approx. 11.3V)
Fault value:
1
Measuring channel for main setpoint / analog select input 1 faulty (terminals 4 and 5)
2
Measuring channel for main actual value faulty (terminals 103 and 104)
3
Measuring channel for analog select input 1 faulty (terminals 6 and 7)
F069
MLFB data are faulty
(active in all operating states)
Possible fault causes
•
Excessive EMC-related interference is present
(e.g. due to unprotected contactors, unscreened cables, loose shield connections)
•
A7009 backplane wiring assembly is defective
Fault value:
1
MLFB code number (r070) = MLFB code number (r070)
is illegal
2
MLFB data checksum error
3
Works number checksum error
4
Number of words of MLFB data is incorrect
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
Description
Further information (r047.002 to r047.016)
r047 Index 002 to 016:
i002 Measured heatsink temperature (16384 .. 100°C)
i003 Measured ADC value
r047 Index 002 to 016:
i002 Incorrect MLFB code number
-
-
-
Faults / Alarms
10-21