Siemens SIMOREG DC Master 6RA7028-6DS22 Operating Instructions Manual page 377

Microprocessor-based converters from 6kw to 1900kw for variable-speed dc drives 6ra70 series
Table of Contents

Advertisement

02.00
Fault
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
Fault value:
Armature current is too low when α=30° and EMF=0.
1
(average armature current <75% of I A, motor or <75% of I A, rated )
Possible cause:
Armature circuit interrupted
High-resistance load
P150 (Alpha G limit) has been set to excessively high value
It was not possible to determine the armature circuit resistance (P110) because the armature current was ≥ 37.5 % of
2
P100 in fewer than 20 of the 150 firing cycles of the measuring phase.
Possible cause:
• Armature current of 37.5% of P100 (I A, motor ) is no longer possible (although a current of 75% of P100 was already
flowing, maybe a fuse has blown).
Armature current peaks are too small at α=30° and EMF=0
3
(armature current peak value <50% of I A, motor or <50% of I A,rated )
Possible cause:
Armature circuit inductance is too high (field supply from armature terminals)
P150 (Alpha G limit) has been set to excessively high value
Possible remedy:
Reduce P100 (I A,motor ) while this optimization run is in progress
4
The armature circuit inductance (P111) cannot be determined from the sampled values of the armature current and line
voltage of the armature current crest last generated
Possible cause:
• P100 (I A,motor ) or r072.i002 (I A,rated ) very much smaller than actual motor rated current of the armature
• L A >327.67mH (armature circuit inductance too large)
• P100 (I A,motor ) very much smaller than r072.i002 (I A,rated )
• Armature circuit short-circuited
5
Offset adjustment of actual field current sensing is not possible
(value detected for P825 is outside permissible value range)
Possible cause:
Fault in actual field current sensing circuit
(defective A7004 gating board or A7001 electronics board)
7
The field circuit resistance (P112) is indeterminable
(the actual field current does not reach the internally specified setpoint of 95% of P102 as a result of P112 variation)
Possible cause:
R A >3276.7Ω
Fault in actual field current sensing circuit (defective gating board or A7001 electronics board)
The command "Inject standstill field" is applied
P102 is set too high
A thyristor in the field bridge is not firing
8
80% of rated EMF (K287=P101 – P100 * P110) cannot be reached within 15s (or maximum of the three set acceleration
times)
Possible cause:
Acceleration time (P303, P307, P311) is set too low
P101 does not match the set maximum speed (U A at n max < P101) or setting for P102 is too low
The command "Ramp-function generator enable"=0 or "Ramp-function generator stop"=1
9
Field current control loop is not stable enough to record field characteristics
(30s after injection of internal field current setpoint, actual field current is deviating by more than (0.39% of P102 + 0.15 %
of r073.002) from the setpoint)
Possible cause:
Field current controller or field current precontrol is not optimized or optimized badly (check P112, P253 to P256 or
execute a current controller optimization run (P051=25))
10
Field characteristic is not uniform
(i.e. in spite of field current setpoint reduction, the flux values of this measuring point calculated from EMF and actual
speed are rising)
Possible cause:
High armature reaction and sharp load variations during recording of field characteristics
Field current controller or field current precontrol is not optimized or optimized badly (check P112, P253 to P256 or
execute a current controller optimization run (P051=25))
SIEMENS AG
6RX1700-0AD76
SIMOREG DC Master
Operating Instructions
Description
Further information (r047.002 to r047.016)
Faults / Alarms
10-13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents