5. PARAMETERS
No.
Symbol
PC38
ERW
Error excessive warning level
Set an error excessive warning level.
To enable the parameter, select "Enabled (1 _ _ _)" of "[AL. 9B Error excessive warning]
selection" in [Pr. PC05].
You can change the setting unit with "Error excessive alarm/error excessive warning level unit
selection" in [Pr. PC06].
Set the level in rev unit. Setting "0" will apply 1 rev. Setting over 200 rev will be clamped with
200 rev.
When an error reaches the set value, [AL. 9B Error excessive warning] will occur. When the
error decreases and becomes lower than the set value, the warning will be canceled
automatically. The minimum pulse width of the warning signal is 100 [ms].
Set values to satisfy the following condition: [Pr. PC38 Error excessive warning level] < [Pr.
PC01 Error excessive alarm level] [AL. 52 Error excessive] will occur first when you set as
follows: [Pr. PC38 Error excessive warning level] ≥ [Pr. PC01 Error excessive alarm level]

5.2.4 I/O setting parameters ([Pr. PD_ _ ])

No.
Symbol
PD02
*DIA2
Input signal automatic on selection 2
Setting digit
HEX.
_ _ _ x
_ _ x _
_ x _ _
x _ _ _
Convert the setting value into hexadecimal as follows.
0 0 0
Name and function
Name and function
BIN.
_ _ _ x
FLS (Upper stroke limit) selection
0: Disabled
1: Enabled
_ _ x _
RLS (Lower stroke limit) selection
0: Disabled
1: Enabled
_ x _ _
For manufacturer setting
x _ _ _
For manufacturer setting
FLS (Upper stroke limit) selection
RLS (Lower stroke limit) selection
BIN 0: Use for an external input signal.
BIN 1: Automatic on
5 - 33
Explanation
Initial value
Signal name
BIN HEX
Initial
value
[unit]
0
[rev]
Initial
value
[unit]
Refer to the
"Name and
Initial
function" column.
value
0h
0h
0h
0h
0
0
0
0
0
Setting
range
0 to
1000
Setting
range