Molded-Case Circuit Breakers, Fuses, Magnetic Contactors - Mitsubishi MR-JE-10B Instruction Manual

Mr-je series
Table of Contents

Advertisement

11. OPTIONS AND PERIPHERAL EQUIPMENT

11.7 Molded-case circuit breakers, fuses, magnetic contactors

CAUTION
When using a fuse instead of the molded-case circuit breaker, use the one having the specifications given in
this section.
Servo amplifier
Power factor
improving reactor is
not used
MR-JE-10B
30 A frame 5 A
MR-JE-20B
MR-JE-40B
30 A frame 10 A
MR-JE-70B
MR-JE-100B
30 A frame 15 A
(3-phase power
supply input)
MR-JE-100B
(1-phase power
30 A frame 15 A
supply input)
MR-JE-200B
30 A frame 20 A
MR-JE-300B
30 A frame 30 A
Note 1. When having the servo amplifier comply with the IEC/EN/UL/CSA standard, refer to app. 4.
2. Use a magnetic contactor with an operation delay time (interval since a current is applied to the coil until the contact closes) of
80 ms or shorter.
3. S-N18 can be used when auxiliary contact is not required.
4. Use a molded-case circuit breaker having the operation characteristics equal to or higher than Mitsubishi Electric general-
purpose products.
The Type E Combination motor controller can also be used instead of a molded-case circuit breaker.
Rated input voltage
Servo amplifier
MR-JE-10B
MR-JE-20B
MR-JE-40B
MR-JE-70B
MR-JE-100B
MR-JE-200B
MR-JE-300B
Select a molded-case circuit breaker with a fast shut-off time to prevent smoke or
a fire.
Always use one molded-case circuit breaker and one magnetic contactor with one
servo amplifier.
Molded-case circuit breaker (Note 1 and 4)
Frame, rated current
Power factor
improving reactor is
used
30 A frame 5 A
30 A frame 5 A
30 A frame 10 A
30 A frame 15 A
30 A frame 20 A
30 A frame 30 A
Input phase
AC [V]
200 to 240
3-phase
Voltage AC
Class
[V]
240
T
Type E Combination motor controller
Rated
Model
voltage
AC [V]
MMP-T32
240
11 - 34
Fuse
Voltage AC
Current [A]
[V]
10
15
20
300
30
40
70
Rated current [A]
(Heater design)
1.6
2.5
4
6.3
8
18
25
Magnetic
contactor
(Note 2)
S-N10
S-T10
S-N20
(Note 3)
S-T21
S-N20
S-T21
SCCR
[kA]
50
25

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents