Writing To The Buffer Memory Of An Intelligent Device Station - Mitsubishi Electric MELSEC-L Special Instructions Manual

Melsec-q/l structured programming manual
Hide thumbs Also See for MELSEC-L:
Table of Contents

Advertisement

Writing to the buffer memory of an intelligent device station

J(P)_RIWT, G(P)_RIWT
CC-Link CC IE C CC IE F
Structured ladder/FBD
J_RIWT
EN
ENO
Jn*
d
s1
s2
The following instruction can go in the dotted squares.
J_RIWT, JP_RIWT, G_RIWT, GP_RIWT
■Executing condition
Instruction
J_RIWT
G_RIWT
JP_RIWT
GP_RIWT
■Argument
Input/output
argument
Input argument
Output argument
Setting
Internal device
*1
data
Bit
(s1)
(s2)
(d)
*1 Local devices and file registers per program cannot be used as setting data.
Processing details
This instruction writes the data for the specified number of points to the buffer memory of the CC-Link module or the device of
the programmable controller CPU module on the specified station.
5 MODULE DEDICATED INSTRUCTION
102
5.4 Network Dedicated Instruction
G_RIWT
EN
ENO
Un*
d
s1
s2
Executing condition
Name
Description
EN
Executing condition
Jn*
Network number of the host station (1 to 239, 254)
254: Network specified in "Valid module during
other station access"
Un*
Start I/O number of the module
(00 to FE: Higher two digits when expressing the I/
O number in three digits)
s1
Variable that stores control data
s2
Start number of the device that stores write data
ENO
Execution result
d
Variable that turns ON upon completion of the
instruction
d[1] also turns ON at the time of error completion.
R, ZR
Word
ST
ENO:=
(EN, Jn*, s1, s2, d);
J_RIWT
ENO:=
(EN, Un*, s1, s2, d);
G_RIWT
J\
U\G
Bit
Word
Data type
Bit
ANY16
ANY16
Array of ANY16 [0..4]
ANY16
Bit
Array of bit [0..1]
Zn
Constant
Others

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec-q

Table of Contents