Mitsubishi Electric MELSEC-L Special Instructions Manual page 128

Melsec-q/l structured programming manual
Hide thumbs Also See for MELSEC-L:
Table of Contents

Advertisement

Processing details
This instruction reads data from a word device of another station.
Setting data
Device
Item
(s1)[0]
Error completion type
(s1)[1]
Completion status
(s1)[2]
Channel used by host
station
(s1)[3]
Target station's CPU
type
(s1)[4]
Target station network
No.
(s1)[5]
Target station No.
(s1)[6]
(s1)[7]
Number of resends
5 MODULE DEDICATED INSTRUCTION
126
5.4 Network Dedicated Instruction
Setting data
...
b15
b7
0
(1)
Error completion type (bit 7)
Specify the clock data setup status at the time of error completion.
0: Clock data at the time of error completion is not set in the area starting from
(s1)[11].
1: Clock data at the time of error completion is set in the area starting from
(s1)[11].
The instruction completion status is stored.
0: Normal completion
Other than 0: Error completion (error code)
Specify the channel used by the host station.
Setting values are as follows.
• Ethernet, MELSECNET/H: 1 to 8
• CC-Link IE Controller Network: 1 to 10
• CC-Link IE Field Network: 1 to 2
Specify the type of the target station CPU.
Setting values are as follows.
■Ethernet
• 0000H: Target station CPU/host system CPU (Specified data are the same as
'03FFH'.)
*1
• 03FFH
: Target station CPU/host system CPU
■MELSECNET/H CC-Link IE
• 0000H: Target station CPU/host system CPU (Specified data are the same as
'03FFH'.)
*2
• 03E0H
: Multi-CPU No. 1/target station CPU (single CPU system)
*2
• 03E1H
: Multi-CPU No. 2
*2
• 03E2H
: Multi-CPU No. 3
*2
• 03E3H
: Multi-CPU No. 4
*1
• 03FFH
: Target station CPU/host system CPU
Specify the network number of the target station.
1 to 239: Network number
254: Specify this when 254 has been set in Jn.
Specify the station number of the target station.
Setting values are as follows.
• MELSECNET/H: 1 to 64
• When the host station is Universal model QCPU in Ethernet or CC-Link IE
Controller Network: 1 to120
• When the host station is anything other than Universal model QCPU in Ethernet
or CC-Link IE Controller Network: 1 to 64
• Master station in CC-Link IE Field Network: 125 (7DH)
• Local station or the intelligent device station in CC-Link IE Field Network: 1 to
120
Reserved
• For instruction execution
Specify the number of instruction resends when the instruction is not completed
within the monitoring time specified in (s1)[8].
• At instruction completion
The number of resends (result) is stored.
...
b0
0
1
Setting
Setting side
range
0001H
User
0081H
System
1 to 10
User
■Ethernet
User
0000H, 03FFH
■MELSECNET
/H, CC-Link IE
0000H, 03E0H
to 03E3H,
03FFH
1 to 239, 254
User
1 to 125
User
0
User
0 to 15
User
System