Mitsubishi Electric MELSEC-L Special Instructions Manual page 153

Melsec-q/l structured programming manual
Hide thumbs Also See for MELSEC-L:
Table of Contents

Advertisement

Setting data
Device
Item
(s)[0]
Execution/error
completion type
(s)[1]
Completion
status
(s)[2]
Host station
channel
(s)[3]
Channel used
by sending
station
(s)[4]
Network No. of
sending station
(s)[5]
Sending station
No.
(s)[6]
(Reserved)
(s)[7]
(Reserved)
(s)[8]
Arrival
monitoring time
(s)[9]
Receive data
length
(s)[10]
(Reserved)
*1
(s)[11]
Clock set flag
(s)[12]
Clock data at
the time of error
*1
(s)[15]
completion
(s)[16]
Error-detected
*1
network No.
Setting data
...
b15
b7
0
(1)
Error completion type (bit 7)
Specify the clock data setup status at the time of error completion.
0: Clock data at the time of error completion is not set in the area starting from (s)[11].
1: Clock data at the time of error completion is set in the area starting from (s)[11].
The instruction completion status is stored.
0: Normal completion
Other than 0: Error completion (error code)
Specify the channel of host station that stores receive data.
Setting values are as follows.
• Ethernet, MELSECNET/H, CC-Link IE Controller Network: 1 to 8
• CC-Link IE Field Network: 1 to 2
Channel used by the sending station is stored.
1 to 8: Channel
Network number of the sending station is stored.
1 to 239: Network number
Station number of the sending station is stored.
Stored values are as follows.
• MELSECNET/H: 1 to 64
• Ethernet, CC-Link IE Controller Network: 1 to 120
• Master station in CC-Link IE Field Network: 125 (7DH)
• Local station or the intelligent device station in CC-Link IE Field Network: 1 to 120
Specify the monitoring time required for the instruction completion. When the
instruction is not completed within the monitoring time, it completes abnormally.
Setting values are as follows.
■Ethernet
• 0 to 16383
• 0 to TCP retransmission timer value: Monitoring is performed by the TCP
retransmission timer value.
• (TCP retransmission timer value + 1) to 16383: Monitoring time (unit: second)
■CC-Link IE MELSECNET/H
• 0 to 32767
• 0: 10 seconds
• 1 to 32767: 1 to 32767 seconds
The number of received data stored in (d1) to (d1)+n is stored.
0: No receive data
1 to 960: Number of words of receive data
Valid/invalid status of the data in the area starting from (s)[12] is stored.
0: Invalid
1: Valid
Clock data at the time of error completion are stored in BCD format.
b15
to
b8 b7
[12 ]
Month (01
to 12
)
s
H
H
[13 ]
Hour (00
to 23
)
s
H
H
[14 ]
Second (00
to 59
)
H
H
s
[15 ]
Year (00
to 99
) First two digits
s
H
H
Network number of the station where an error was detected is stored. (However,
when an error was detected at the host station, the network number is not stored.)
1 to 239: Network number
...
b0
0
to
b0
Year (00
to 99
) Last two digits
H
H
Day (01
to 31
)
H
H
Minute (00
to 59
)
H
H
Day of week (00
to 06
)
H
H
00
(Sun.) to 06
(Sat.)
H
H
5 MODULE DEDICATED INSTRUCTION
5.4 Network Dedicated Instruction
Setting
Setting side
range
0000H, 0080H
User
System
1 to 8
User
System
System
System
0 to 32767
User
System
System
System
System
151