Mitsubishi Electric MELSEC-L Special Instructions Manual page 161

Melsec-q/l structured programming manual
Hide thumbs Also See for MELSEC-L:
Table of Contents

Advertisement

Device
Item
(s1)[8]
Arrival
monitoring time
(s1)[9]
Request data
length
(s1)[10]
Response data
length
*3
(s1)[11]
Clock set flag
(s1)[12]
Clock data on
error
*3
(s1)[15]
completion
(s1)[16]
Error-detected
*3
network No.
(s1)[17]
Error-detected
*3
station No.
*1 Specification is possible when the host station is a network module or Ethernet module of function version D or later.
(Specification is not possible for other modules. An access is always made to the target station CPU.)
*2 Specification is possible when the versions of the QCPU and the network module on the host station and the target station are as
indicated below.
(Specification is not possible for other modules. An access is always made to the target station CPU.)
 Network module: The first five digits of the serial number are '06092' or higher.
 QCPU: The first five digits of the serial number are '06092' or higher.
*3 This becomes valid only when 1 is set in bit 7 of Error completion type ((s1)[0]).
Setting data
Specify the monitoring time required for the instruction completion.
If the instruction is not completed within this time, it is resent by the number of times
specified in (s1)[7].
Setting values are as follows.
■Ethernet
• 0 to 16383
• 0 to TCP retransmission timer value: Monitoring is performed by the TCP
retransmission timer value.
• (TCP retransmission timer value + 1) to 16383: Monitoring time (unit: second)
■MELSECNET/H CC-Link IE
• 0 to 32767
• 0: 10 seconds
• 1 to 32767: 1 to 32767 seconds
Specify the number of request data (words).
(Number of words of data stored in the request data storage device (s2))
4: Remote RUN
3: Remote STOP
2: Clock data read
6: Clock data write
Number of response data (words) are stored.
(Number of words of the data stored in response data storage device)
2: Remote RUN/STOP
6: Clock data read
2: Clock data write
Valid/invalid status of the data in the area starting from (s1)[12] is stored.
0: Invalid
1: Valid
Clock data at the time of error completion are stored in BCD format.
b15
to
b8 b7
Month (01
to 12
)
[12 ]
s1
H
H
Hour (00
to 23
)
s1
[13 ]
H
H
Second (00
to 59
)
[14 ]
s1
H
H
Year (00
to 99
) First two digits
[15 ]
s1
H
H
Network number of the station where an error was detected is stored. (However,
when an error was detected at the host station, the network number is not stored.)
1 to 239: Network number
Number of the station where an error was detected is stored. (However, when an
error was detected at the host station, the network number is not stored.)
Stored values are as follows.
• MELSECNET/H: 1 to 64
• Ethernet, CC-Link IE Controller Network: 1 to 120
• Master station in CC-Link IE Field Network: 125 (7DH)
• Slave station in CC-Link IE Field Network: 1 to 120
to
b0
Year (00
to 99
) Last two digits
H
H
Day (01
to 31
)
H
H
Minute (00
to 59
)
H
H
Day of week (00
to 06
)
H
H
00
(Sun.) to 06
(Sat.)
H
H
5 MODULE DEDICATED INSTRUCTION
5.4 Network Dedicated Instruction
Setting
Setting side
range
0 to 32767
User
2 to 4, 6
User
System
System
System
System
System
159