Long Range Radio Connected to the J7 Triggers

These triggers may be used to trip auxiliary alarm
signaling equipment such as the 7720, 7720ULF, and
7920SE Long Range Radios.
The triggers are common to all partitions and must be
enabled for each partition (field 2✳20).

Installing a 4100SM

The 4100SM is used to print event log reports to a
serial printer.
NOTE: See SECTION 4: Programming for the
programming details when using the 4100SM.
Serial Printer Configurations
Configure the serial printer as follows:
8 data bits, no parity, 1 stop bit
300 or 1200 baud
Connecting the 4100SM to a Serial Printer
To connect a serial printer using the 4100SM, refer to
Figure 3-25 and perform the following steps:
Action
Step
Connect terminal 1 on the 4100SM to the
1
Violet wire on the 4142TR cable.
Connect terminal 6 on the 4100SM to the
2
Brown wire on the 4142TR cable.
Connect the 4142TR cable to J8 on the
3
control.
Connect terminals 8 and 7 of the 4100SM to
4
terminals 6 and 7 (aux. power (+) and (-)),
respectively of the control.
Connect the UL EDP Listed serial printer to
5
the 4100SM Interface Module.
The 4100SM Module is supplied with a 10-
foot RS232 cable. A longer cable can be used
if the VISTA-50P/VISTA-50PUL is separated
from the serial printer by more than 10 feet,
but the total cable length should be less than
50 feet.

Installing the 4285/4286 VIP Module

The 4285/4286 VIP Module is an add-on accessory that
permits the user to access the security system (and
relays) via a TouchTone telephone. This may be done
either from the premises or by calling the premises from
a remote location. Only one VIP Module can be used in
a security system. This module must be enabled as
Device Address 4 in the Device Programming in #93
Menu Mode, and must be assigned to a partition.
The 4285/4286 VIP Module is not permitted in
U L
UL installations.
3-20
WWW.DIYALARMFORUM.COM
The fire and burglary/audible panic alarm triggers are
normally LOW and go HIGH until a User Code + OFF
is entered in all enabled partition(s) that display these
conditions.
The silent panic/duress trigger latches HIGH, except for
duress, which is momentary.
Refer to the installation instructions that accompany
your radio for the connections to the control panel.
1
2
3
4
5
6
7
8
NU
To TB6 Aux. Power (+)
To TB7 Aux. Power (-)
4100SM JUMPERS
(CUT TO SET RESPECTIVE SIGNAL FLOATING)
COLOR
FUNCTION
PIN #
RED
CD
8
BLUE
CTS
5
WHITE
DSR
6

Figure 3-25: 4100SM Using a Serial Printer

NOTE: See the 4100SM Installation Instructions for
details concerning the serial printer operation.
Detailed operating instructions for phone access
to the security system are provided with the VIP
Module.
9
J8 CONNECTOR
4142TR CABLE (SUPPLIED WITH 4100SM)
4100SM SERIAL MODULE
8
+ PWR
(25mA current draw)
7
- (GND)
6
RXD
5
not used
4
not used
3
TXD
2
not used
1
DTR
RED
BLUE
USE GENDER CHANGER
3M
Cable
SUPPLIED WITH 4100SM
Supplied with
IF PRINTER HAS DB25
4100SM
MALE CONNECTOR
SERIAL PRINTER
SET FOR: 8 DATA BITS
EVEN PARITY
STOP BIT
300/1200 BAUD
WHITE