5.6 Copy Function Related Displays

5.6

Copy Function Related Displays

u

Tasks, Errors, and Troubleshooting

The table below lists the messages and errors that may appear when using the Copy function.
When executing the tasks offered by the Copy function, the operator will indicate the task being performed. When an error
occurs, a code appears on the operator to indicate the error. Note that errors related to the Copy function do not trigger a multi-
function output terminal that has been set up to close when a fault or alarm occurs. To clear an error, simply press any key on
the operator and the error display will disappear.
Table 5.6
lists the corrective action that can be taken when an error occurs.
Note: 1. Whenever using the copy function, the drive should be fully stopped.
2. The drive will not accept a Run command while the Copy function is being executed.
3. Parameters can only be saved to a drive when the voltage class, capacity, control mode, and software version match.
Digital Operator Display
u

Fault Reset Methods

When a fault occurs, the cause of the fault must be removed and the drive must be restarted. The table below lists the different
ways to restart the drive.
After the Fault Occurs
Fix the cause of the fault, restart the drive, and
reset the fault
Resetting via Fault Reset Digital Input S4
Turn off the main power supply if the above methods do not reset the fault. Reapply power after the
digital operator display has turned off.
Note: If the Run command is present, the drive will disregard any attempts to reset the fault. Remove the Run command before attempting to clear a
fault situation.
148
Table 5.6 Copy Function Task and Error Displays
CoPy
Writing Parameter Settings (flashing)
CPEr
Control Mode Mismatch
CPyE
Error Writing Data
CSEr
Copy Unit Error
dFPS
Drive Model Mismatch
End
Task Complete
iFEr
Communication Error
ndAT
Model, Voltage Class, Capacity Mismatch
rdEr
Error Reading Data
rEAd
Reading Parameter Settings (flashing)
vAEr
Voltage Class, Capacity Mismatch
vFyE
Parameter settings in the drive and those saved to the copy function are not the same
vrFy
Comparing Parameter Settings (flashing)
Press
on the digital operator.
Close then open the fault signal digital input via
terminal S4. S4 is set for "Fault Reset" as default
(H1-04 = 14).
Procedure
YASKAWA ELECTRIC TOEP C710616 41B YASKAWA AC Drive - A1000 Quick Start Guide
Task
- MODE -
RESET
ESC
RESET
Fault Reset Switch
S4 Fault Reset Digital Input
SC Digital Input Common
ON
2
OFF
1
DRV
oC
Overcurrent
RESET
FWD
F1
F2
LO
RE
ENTER
RUN
STOP
Drive