YASKAWA A1000 Technical Manual page 209

Hide thumbs Also See for A1000:
Table of Contents

Advertisement

H2-oo
Function
Setting
15
Frequency detection 3
16
Frequency detection 4
17
Torque detection 1 (N.C.)
18
Torque detection 2 (N.O.)
19
Torque detection 2 (N.C.)
1A
During reverse
1B
During baseblock (N.C.)
1C
Motor 2 selection
1D
During regeneration
1E
Restart enabled
1F
Motor overload alarm (oL1)
20
Drive overheat pre-alarm (oH) Closed: Heatsink temperature exceeds the parameter L8-02 value.
Mechanical weakening
22
detection
2F
Maintenance period
30
During torque limit
31
During speed limit
During speed limit in Torque
32
Control
33
Zero Servo complete
37
During frequency output
38
Drive enabled
39
Watt hour pulse output
3C
LOCAL/REMOTE status
3D
During speed search
3E
PID feedback low
3F
PID feedback high
4A
During KEB Ride-Thru
4B
During short circuit braking
4C
During fast stop
4D
oH Pre-alarm time limit
4E
Braking transistor fault (rr)
4F
Braking resistor overheat (oH)
60
Internal cooling fan alarm
Rotor position detection
61
complete
DriveWorksEZ
90 to 92
digital outputs 1 to 3
Function 0 to 92 with inverse
100 to 192
output
YASKAWA ELECTRIC TOEP C710616 41B YASKAWA AC Drive - A1000 Quick Start Guide
H2 Multi-Function Digital Output Settings
Closed: When the drive output frequency is less than or equal to the value in L4-03 ±L4-04.
Closed: When the output frequency is greater than or equal to the value in L4-03 ±L4-04.
Open: Overtorque or undertorque has been detected.
Closed: Overtorque or undertorque has been detected.
Open: Overtorque or undertorque has been detected.
Closed: Drive is running in the reverse direction.
Open: Drive has entered the baseblock state (no output voltage).
Closed: Motor 2 is selected by a digital input (H1-oo = 16)
Closed: Motor is regenerating energy into the drive.
Closed: An automatic restart is performed
Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers this alarm.
Closed: Mechanical weakening detected.
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay may require
maintenance.
Closed: When the torque limit has been reached.
Closed: Speed limit has been reached.
Closed: Speed limit has been reached while using Torque Control.
Closed: Zero Servo operation has finished.
Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial Excitation is
being performed.
Closed: Drive is running the motor (not in a baseblock state and DC Injection is not being
performed).
Closed: Multi-function input set for "Drive enable" is closed (H1-oo = 6A)
Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate the kWh count.
Open: REMOTE
Closed: LOCAL
Closed: Speed Search is being executed.
Closed: PID feedback level is too low.
Closed: The PID feedback level is too high.
Closed: KEB Ride-Thru is being performed.
Closed: Short Circuit Braking is active.
Closed: A Fast Stop command has been entered from the operator or input terminals.
Closed: oH pre-alarm time limit has passed.
Closed: The built-in dynamic braking transistor failed.
Note: This function is not available in models CIMR-Ao4A0930 and 4A1200.
Closed: The dynamic braking resistor has overheated.
Note: This function is not available in models CIMR-Ao4A0930 and 4A1200.
Closed: Internal cooling fan alarm
Closed: Drive has successfully detected the rotor position of the PM motor.
Reserved for DWEZ digital output functions.
Inverts the output switching of the multi-function output functions.
Set the last two digits of 1oo to reverse the output signal of that specific function.
B.7 H Parameters: Multi-Function Terminals
Description
Page
B
209