Three-Phase 400 V Class Drive Models Cimr-Ao4A0208 To 4A1200 - YASKAWA A1000 Technical Manual

Hide thumbs Also See for A1000:
Table of Contents

Advertisement

A.2 Power Ratings
u

Three-Phase 400 V Class Drive Models CIMR-Ao4A0208 to 4A1200

Item
CIMR-Ao4A
Maximum Applicable Motor
<1>
Capacity (HP)
Input Current (A)
Rated Voltage
Input
Rated Frequency
Allowable Voltage Fluctuation
Allowable Frequency Fluctuation
Input Power (kVA)
Rated Output Capacity
<4>
(kVA)
Rated Output Current
(A)
Output
Overload Tolerance
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring conditions,
and power supply impedance.
<3> DC is not available for UL/CE standards.
<4> Rated motor capacity is calculated with a rated output voltage of 440 V.
<5> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<6> Carrier frequency can be increased to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.
168
Table A.7 Power Ratings Continued (Three-Phase 400 V Class)
0208
ND Rating
150
HD Rating
125-150
ND Rating
207
<2>
HD Rating
170
ND Rating
189
HD Rating
155
<5>
159
ND Rating
137
HD Rating
<6>
<5>
208
ND Rating
180
HD Rating
<6>
User-adjustable between 1 and 10 kHz
0250
0296
0362
200
250
300
150
200
250
248
300
346
207
248
300
Three-phase: 380 to 480 Vac 50/60 Hz/510 to 680 Vdc
227
274
316
189
227
274
191
226
276
165
198
232
<6>
<6>
<6>
250
296
362
216
260
304
<6>
<6>
<6>
ND Rating: 120% of rated output current for 60 s
HD Rating: 150% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Three-phase: 380 to 480 V (proportional to input voltage)
400 Hz (user-adjustable)
YASKAWA ELECTRIC TOEP C710616 41B YASKAWA AC Drive - A1000 Quick Start Guide
Specification
0414
0515
0675
350
400-450 500-550
400-450-
300
350
500
410
465
657
346
410
584
-15 to 10%
±5%
375
425
601
316
375
534
316
392
514
282
343
461
<5>
<5>
<5>
414
515
675
370
450
605
<5>
<5>
<5>
User-adjustable between 1 and 5
kHz
0930
1200
750
1000
650
900
922
1158
830
1031
<3>
843
1059
759
943
709
915
617
831
<5>
<5>
930
1200
810
1090
<5>
<5>
2 kHz
0.95 × [input
voltage]
150 Hz (user-
adjustable)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents