B.12 T: Motor Tuning
Enter data into the following parameters to tune the motor and drive for optimal performance.
u

T1: Induction Motor Auto-Tuning

No.
(Addr.
Name
Hex)
T1-00
Motor 1/Motor 2 Selection
(700)
T1-01
Auto-Tuning Mode
(701)
Selection
<1>
T1-02
Motor Rated Power
(702)
T1-03
Motor Rated Voltage
(703)
T1-04
Motor Rated Current
(704)
T1-05
Motor Base Frequency
(705)
T1-06
Number of Motor Poles
(706)
T1-07
Motor Base Speed
(707)
T1-08
PG Number of Pulses Per
(708)
Revolution
T1-09
Motor No-Load Current
(709)
(Stationary Auto-Tuning)
T1-10
Motor Rated Slip (Stationary
(70A)
Auto-Tuning)
T1-11
Motor Iron Loss
(70B)
<1> The availability of certain Auto-Tuning methods depends on the control mode selected for the drive.
<2> Default setting is determined by parameter A1-02, Control Method Setting.
<3> Default setting is dependent on parameter o2-04, Drive Model Selection.
<4> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<5> Default setting value differs depending on the motor code value and motor parameter settings.
YASKAWA ELECTRIC TOEP C710616 41B YASKAWA AC Drive - A1000 Quick Start Guide
Description
1: Motor 1 (sets E1-oo, E2-oo)
2: Motor 2 (sets E3-oo, E4-oo)
0: Rotational Auto-Tuning
1: Stationary Auto-Tuning 1
2: Stationary Auto-Tuning for Line-to-Line Resistance
3: Rotational Auto-Tuning for V/f Control (necessary for Energy Savings and
Speed Estimation Speed Search)
4: Stationary Auto-Tuning 2
8: Inertia Tuning (perform Rotational Auto-Tuning prior to Inertia Tuning)
9: ASR Gain Tuning (perform Rotational Auto-Tuning prior to ASR Gain
Auto-Tuning)
Sets the motor rated power as specified on the motor nameplate.
Note: Use the following formula to convert horsepower into kilowatts: kW
= HP x 0.746.
Sets the motor rated voltage as specified on the motor nameplate.
Sets the motor rated current as specified on the motor nameplate.
Sets the rated frequency of the motor as specified on the motor nameplate.
Sets the number of motor poles as specified on the motor nameplate.
Sets the rated speed of the motor as specified on the motor nameplate.
Sets the number of pulses per revolution for the PG being used (pulse generator
or encoder).
Sets the no-load current for the motor. After setting the motor capacity to T1-02
and the motor rated current to T1-04, this parameter will automatically display
the no-load current for a standard 4-pole Yaskawa motor. Enter the no-load
current as indicated on the motor test report.
Sets the motor rated slip. After setting the motor capacity to T1-02, this
parameter will automatically display the motor slip for a standard 4-pole
Yaskawa motor. Enter the motor slip as indicated on the motor test report.
Sets the iron loss for determining the Energy Saving coefficient.
The value is set to E2-10 (motor iron loss) set when the power is cycled. If
T1-02 is changed, a default value appropriate for the motor capacity that was
entered will appear.
B.12 T: Motor Tuning
Values
Page
Default: 1
Range: 1, 2
Default: 0
Range: 0 to 4; 8, 9
<2>
<3>
Default:
Min.: 0.00 kW
Max.: 650.00 kW
Default: 200.0 V
<4>
Min: 0.0
<4>
Max: 255.0
<3>
Default:
Min.: 10% of drive
rated current
Max.: 200% of
drive rated current
Default: 60.0 Hz
Min.: 0.0
Max.: 400.0
Default: 4
Min.: 2
Max.: 48
Default: 1750 r/min
Min.: 0
Max.: 24000
Default: 1024 ppr
Min.: 1
Max.: 60000
Default: –
Min.: 0 A
Max.: T1-04
Default: –
Min.: 0.00 Hz
Max.: 20.00 Hz
<5>
Default: 14 W
Min.: 0
Max.: 65535
227
B