◆ Copy Function Related Displays

Tasks, Errors, and Troubleshooting
The table below lists the messages and errors that may appear when using the Copy function.
When executing the tasks offered by the Copy function, the operator will indicate the task being performed. When an
error occurs, a code appears on the operator to indicate the error. Note that errors related to the Copy function do not
trigger a multi-function output terminal that has been set up to close when a fault or alarm occurs. To clear an error,
simply press any key on the operator and the error display will disappear.
Table 53
lists the corrective action that can be taken when an error occurs.
Note: 1. Whenever using the copy function, the drive should be fully stopped.
2. The drive will not accept a Run command while the Copy function is being executed.
3. Parameters can only be saved to a drive when the voltage class, capacity, control mode, and software version match.
Digital Operator Display
Fault Reset Methods
When a fault occurs, the cause of the fault must be removed and the drive must be restarted. The table below lists the
different ways to restart the drive.
After the Fault Occurs
Fix the cause of the fault, restart the
drive, and reset the fault
Resetting via Fault Reset Digital
Input S4
If the above methods do not reset the fault, turn off the drive main power supply.
Reapply power after the digital operator display is out.
Note: If the Run command is present, the drive will disregard any attempts to reset the fault. The Run command must first be removed
before a fault situation can be cleared.
YASKAWA ELECTRIC TOEP C710616 21C YASKAWA AC Drive - A1000 Quick Start Guide
Table 53 Copy Function Task and Error Displays
CoPy
Writing Parameter Settings (flashing)
CPEr
Control Mode Mismatch
CPyE
Error Writing Data
CSEr
Copy Unit Error
dFPS
Drive Model Mismatch
End
Task Complete
iFEr
Communication Error
ndAT
Model, Voltage Class, Capacity Mismatch
rdEr
Error Reading Data
rEAd
Reading Parameter Settings (flashing)
vAEr
Voltage Class, Capacity Mismatch
Parameter settings in the drive and those saved to the copy function are not the same
vFyE
vrFy
Comparing Parameter Settings (flashing)
Procedure
Press
on the digital operator.
Close then open the fault signal digital input via
terminal S4. S4 is set for "Fault Reset" as
default (H1-04 = 14).
5 Troubleshooting
Task
YEC_
DIGITAL OPERATOR JVOP-182
REV
common
ESC
RESET
Drive
Fault Reset Switch
S4 Fault Reset Digital Input
SC Digital Input Common
ON
2
OFF
1
ALM
DRV
FOUT
LO
RE
ENTER
RUN
STOP
5
117