Sinking/Sourcing Mode Selection For Safe Disable Inputs; Using The Pulse Train Output - YASKAWA A1000 Technical Manual

Hide thumbs Also See for A1000:
Table of Contents

Advertisement

u

Sinking/Sourcing Mode Selection for Safe Disable Inputs

Note: Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to EN61800-5-1, ISO13849
Cat. 3, IEC/EN61508 SIL2, Insulation coordination: class 1.
Use jumper S3 on the terminal board to select between Sink mode, Source mode or external power supply for the Safe Disable
inputs H1 and H2 as shown in
Table 3.12 Safe Disable Input Sink/Source/External Power Supply Selection
Mode
Sinking Mode
Sourcing Mode
u

Using the Pulse Train Output

The pulse train output terminal MP can supply power or be used with an external power supply.
NOTICE: Connect peripheral devices in accordance with the specifications. Failure to comply may cause unexpected drive operation, and
can damage the drive or connected circuits.
n
Using Power from the Pulse Output Terminal (Source Mode)
The high voltage level of the pulse output terminal depends on the load impedance.
Load Impedance R
Note: The load resistance needed in order to get a certain high level voltage V
YASKAWA ELECTRIC TOEP C710616 41B YASKAWA AC Drive - A1000 Quick Start Guide
Table 3.11
(Default: Source mode, internal power supply).
Drive Internal Power Supply
Jumper S3
24 Vdc
HC
H1
H2
Jumper S3
24 Vdc
HC
H1
H2
(kΩ)
L
1.5 kΩ
4 kΩ
10 kΩ
MP
AC
Figure 3.31 Pulse Output Connection Using Internal Voltage Supply
External
24 Vdc
External
24 Vdc
Output Voltage V
can be calculated by: R
MP
Load Impedance
V
R
MP
L
3.8 Control I/O Connections
External 24 Vdc Power Supply
Jumper S3
24 Vdc
HC
H1
H2
Jumper S3
24 Vdc
HC
H1
H2
(V) (insulated)
MP
5 V
8 V
10 V
• 2 / (12 – V
= V
)
L
MP
MP
3
67