YASKAWA A1000 Technical Manual page 106

Hide thumbs Also See for A1000:
Table of Contents

Advertisement

4.6 Basic Drive Setup Adjustments
Setting
A
Run Command Source
B
Torque Detection 1 (N.O.)
C
Frequency Reference Loss
<1>
Braking Resistor Fault
D
E
Fault
F
Through Mode
10
Minor Fault
11
Fault Reset Command Active
12
Timer Output
13
Speed Agree 2
14
User-Set Speed Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
17
Torque Detection 1 (N.C.)
18
Torque Detection 2 (N.O.)
19
Torque Detection 2 (N.C.)
1A
During Reverse
1B
During Baseblock (N.C.)
1C
Motor 2 Selection
1D
During regeneration
1E
Restart Enabled
1F
Motor Overload Alarm (oL1)
20
Drive Overheat Pre-Alarm (oH)
22
Mechanical Weakening Detection
2F
Maintenance Period
<1> Not available in models CIMR-Ao4A0930 amd 4A1200.
<2> Not available in models CIMR-Ao2A0169 to 2A0415 and 4A0088 to 4A1200.
Setting 2: Speed Agree 1 (f
Closes when the actual output frequency or motor speed (CLV, CLV/PM) is within the Speed Agree Width (L4-02) of the
current frequency reference regardless of the direction.
Status
Open
Output frequency or motor speed does not match the frequency reference while the drive is running.
Closed
Output frequency or motor speed is within the range of frequency reference ±L4-02.
Note: Detection works in forward and reverse.
Setting 3: User-Set Speed Agree 1 (f
Closes when the actual output frequency or motor speed (CLV, CLV/PM) and the frequency reference are within the speed
agree width (L4-02) of the programmed speed agree level (L4-01).
106
Function
/f
Agree 1)
ref
out
Frequency
reference
Output Frequency
or Motor Speed
OFF
Speed agree 1
ON
Figure 4.24 Speed Agree 1 Time Chart
/f
Agree 1)
ref
set
Page
Setting
30
During Torque Limit
31
During Speed Limit
32
During Speed Limit in Torque Control
33
Zero Servo Complete
37
During Frequency Output
38
Drive Enabled
39
Watt Hour Pulse Output
3C
LOCAL/REMOTE Status
3D
During Speed Search
3E
PID Feedback Low
3F
PID Feedback High
4A
During KEB Operation
4B
During Short Circuit Braking
4C
During Fast Stop
4D
oH Pre-Alarm Time Limit
<2>
Braking Transistor Fault (rr)
4E
<2>
Braking Resistor Overheat (rH)
4F
60
Internal Cooling Fan Alarm
61
Rotor Position Detection Completed
90
DriveWorksEZ Digital Output 1
91
DriveWorksEZ Digital Output 2
92
DriveWorksEZ Digital Output 3
100 to 192 Functions 0 to 92 with Inverse Output
Description
L4-02
YASKAWA ELECTRIC TOEP C710616 41B YASKAWA AC Drive - A1000 Quick Start Guide
Function
L4-02
Page

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents