YASKAWA A1000 Technical Manual page 204

Hide thumbs Also See for A1000:
Table of Contents

Advertisement

B.6 F: Options
No.
(Addr.
Name
Hex)
F7-14
Duplex Mode Selection
(3F2)
F7-15
Communication Speed
(3F3)
Selection
F7-16
Communication Loss
(3F4)
Timeout
F7-17
EtherNet/IP Speed Scaling
(3F5)
Factor
F7-18
EtherNet/IP Current Scaling
(3F6)
Factor
F7-19
EtherNet/IP Torque Scaling
(3F7)
Factor
F7-20
EtherNet/IP Power Scaling
(3F8)
Factor
F7-21
EtherNet/IP Voltage Scaling
(3F9)
Factor
F7-22
EtherNet/IP Time Scaling
(3FA)
F7-23 to
F7-32
Dynamic Output Assembly
(3FB to
Parameters
374)
F7-33 to
F7-42
Dynamic Input Assembly
(375 to
Parameters
37E)
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Cycle power for setting changes to take effect.
<3> If F7-13 is set to 0, all IP addresses (F7-01 to F7-04) must be unique.
204
Selects duplex mode setting.
0: Half duplex forced
1: Auto-negotiate duplex mode and communication speed
2: Full duplex forced
Sets the communication speed
10: 10 Mbps
100: 100 Mbps
Sets the timeout value for communication loss detection in tenths of a second.
A value of 0 disables the connection timeout.
Example: An entered value of 100 represents 10.0 seconds.
Sets the scaling factor for the speed monitor in EtherNet/IP Class ID 2AH
Object.
Sets the scaling factor for the output current monitor in EtherNet/IP Class ID
2AH Object.
Sets the scaling factor for the torque monitor in EtherNet/IP Class ID 2AH
Object.
Sets the scaling factor for the power monitor in EtherNet/IP Class ID 2AH
Object.
Sets the scaling factor for the voltage monitor in EtherNet/IP Class ID 2AH
Object.
Sets the scaling factor for the time monitor in EtherNet/IP Class ID 2AH
Object.
Parameters used in Output Assembly 116. Each parameter contains a
MEMOBUS/Modbus address. The value received for Output Assembly 116
will be written to this corresponding MEMOBUS/Modbus address. A
MEMOBUS/Modbus address value of 0 means that the value received for
Output Assembly 116 will not be written to any MEMOBUS/Modbus register.
Parameters used in Input Assembly 166. Each parameter contains a
MEMOBUS/Modbus address. The value sent for Input Assembly 166 will be
read from this corresponding MEMOBUS/Modbus address. A MEMOBUS/
Modbus address value of 0 means that the value sent for Input Assembly 166
is not defined by the user, therefore the option default register value will be
returned.
YASKAWA ELECTRIC TOEP C710616 41B YASKAWA AC Drive - A1000 Quick Start Guide
Description
Values
Page
Default: 1
Range: 0 to 2
Default: 10
Range: 10, 100
Default: 0
Min.: 0
Max.: 300
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Default: 0