YASKAWA A1000 Technical Manual page 181

Hide thumbs Also See for A1000:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
b5-08
PID Primary Delay Time
(1AC)
Constant
b5-09
PID Output Level Selection 0: Normal output (direct acting)
(1AD)
b5-10
PID Output Gain Setting
(1AE)
b5-11
PID Output Reverse
(1AF)
Selection
b5-12
PID Feedback Loss
(1B0)
Detection Selection
b5-13
PID Feedback Loss
(1B1)
Detection Level
b5-14
PID Feedback Loss
(1B2)
Detection Time
b5-15
PID Sleep Function Start
(1B3)
Level
b5-16
PID Sleep Delay Time
(1B4)
b5-17
PID Accel/Decel Time
(1B5)
b5-18
PID Setpoint Selection
(1DC)
b5-19
PID Setpoint Value
(1DD)
b5-20
PID Setpoint Scaling
(1E2)
b5-34
(19F)
PID Output Lower Limit
b5-35
(1A0)
PID Input Limit
b5-36
PID Feedback High
(1A1)
Detection Level
b5-37
PID Feedback High
(1A2)
Detection Time
b5-38
PID Setpoint User Display
(1FE)
YASKAWA ELECTRIC TOEP C710616 41B YASKAWA AC Drive - A1000 Quick Start Guide
Description
Sets a low pass filter time constant on the output of the PID controller.
1: Reverse output (reverse acting)
Sets the gain applied to the PID output.
0: Negative PID output triggers zero limit.
1: Rotation direction reverses with negative PID output.
Note: When using setting 1, make sure reverse operation is permitted by
b1-04.
0: No fault. Digital output only.
1: Fault detection. Alarm output, drive continues operation.
2: Fault detection. Fault output, drive output is shut off.
3: No fault. Digital output only. No fault detection when PID control is
disabled.
4: Fault detection. Alarm is triggered and drive continues to run. Fault
detection even when PID is disabled.
5: Fault detection. Drive output shuts off. No fault detection when PID control
is disabled.
Sets the PID feedback loss detection level as a percentage of the maximum
output frequency.
Sets a delay time for PID feedback loss.
Sets the frequency level that triggers the sleep function.
Sets a delay time before the sleep function is triggered.
Sets the acceleration and deceleration time to PID setpoint.
0: Disabled
1: Enabled
Sets the PID target value when b5-18 = 1. Set as a percentage of the maximum
output frequency.
0: 0.01 Hz units
1: 0.01% units (100% = max output frequency)
2: r/min (number of motor poles must entered)
3: User-set (set scaling to b5-38 and b5-39)
Sets the minimum output possible from the PID controller as a percentage of
the maximum output frequency.
Limits the PID control input (deviation signal) as a percentage of the maximum
output frequency. Acts as a bipolar limit.
Sets the PID feedback high detection level as a percentage of the maximum
output frequency.
Sets the PID feedback high level detection delay time.
Sets the display value of U5-01 and U5-04 when the maximum frequency is
output.
B.2 b: Application
Values
Page
Default: 0.00 s
Min.: 0.00
Max.: 10.00
Default: 0
Range: 0, 1
Default: 1.00
Min.: 0.00
Max.: 25.00
Default: 0
Range: 0, 1
Default: 0
Range: 0 to 5
Default: 0%
Min.: 0
Max.: 100
Default: 1.0 s
Min.: 0.0
Max.: 25.5
<1>
Default:
Min.: 0.0 Hz
Max.: 400.0 Hz
Default: 0.0 s
Min.: 0.0
Max.: 25.5
Default: 0.0 s
Min.: 0.0
Max.: 6000.0
Default: 0
Range: 0, 1
Default: 0.00%
Min.: 0.00
Max.: 100.00
Default: 1
Range: 0 to 3
Default: 0.00%
Min.: -100.00
Max.: 100.00
Default: 1000.0%
Min.: 0.0
Max.: 1000.0
Default: 100%
Min.: 0
Max.: 100
Default: 1.0 s
Min.: 0.0
Max.: 25.5
<2>
Default:
Min.: 1
Max.: 60000
181