3.1 Using the Web Application to Change the GX/GP Settings, Monitor Data, and Control the GX/GP (Web server function)
3.1.4
Monitoring the GX/GP Data and Controlling the GX/GP from the Monitor
Screen
Switching the Monitor Display
Procedure
3-16
You can retrieve data and display conditions from the GX/GP and view the information using
the monitors listed below. You can also perform alarm acknowledge and other operations.
Monitors Trend, digital, bar graph, horizontal bar graph, overview, alarm summary,
message summary, DO channel status, internal switch status, Modbus master
status, Modbus client status, WT client status, memory data list, report data list,
manual sampled data list, various logs, network information, system information,
favorite monitor, and SLMP client status
On the trend monitor, digital monitor, bar graph monitor, and horizontal bar graph monitor,
channel data is displayed in groups. Up to 4 groups can be displayed.
The favorite monitor is a monitor that displays up to four monitors (except for network
information and system information) on a single screen (this is different from the favorite
screen registration function of the GX/GP).
Display Update Interval
The channel data display is updated at the scan interval. However, the shortest update
interval is 1 second.
Order of Display Precedence
If the display of the same type of items overlaps, the information of the smallest number
takes precedence. For example, if multiple alarms are occurring, the alarm with the smallest
alarm level number takes precedence.
Note
If the GX/GP system configuration or settings change while the monitor is displayed, the monitor
may not display data correctly. In such a case, reload the page.
On the Data tab, click the monitor you want to display. Favorite monitors appears when
you register a favorite monitor.
You can also switch the screen by clicking a monitor display switch button.
Data tab tree
Switch the monitor display
Change the channel display format
Pause and resume data updating