Setting The Burnout Criteria (Release Number 2 And Later); Setting The Chattering Filter (Di Module) For Pulse Input - YOKOGAWA GX20 User Manual

Smartdac plus paperless recorder
Hide thumbs Also See for GX20:
Table of Contents

Advertisement

1.11 Setting Measurement Conditions (Scan interval, A/D integrate, etc.)
1.11.6
Setting the Burnout Criteria (Release number 2 and later)
Path
Description
1.11.7
Setting the Chattering Filter (DI module) for Pulse Input
Path
Description
Explanation
1-124
Set the upper and lower limits for determining burnout for when the range type is set to GS
or GS (4-20mA).
GX/GP: MENU key > Browse tab > Setting > Setting menu Measurement settings >
Select unit Main unit or Unit1 to 6 > Module 0 to 9
Web application: Config. tab > Measurement settings > Module operation settings
Hardware configurator: Measurement settings > Module operation settings
1 The module numbers that appear depend on the GX/GP module configuration.
General signal
Setup Item
Lower limit of burnout
Upper limit of burnout
1 When the PID control module, lower limit: -20.0, upper limit: 120.0.
Lower Limit of Burnout
Set the lower limit for determining burnout.
Set as a percentage of the specified span width.
Upper Limit of Burnout
Set the upper limit for determining burnout.
Set as a percentage of the specified span width.
You can set this filter on a DI module or DI/DO module when the GX/GP (/MT option)
operation mode is set to Normal.
For details on the chattering filter of pulse input modules, see page 1-63 in section 1.4.1,
"Setting the Range".
GX/GP: MENU key > Browse tab > Setting > Setting menu Measurement settings >
Select unit Main unit or Unit1 to 6 > Module 0 to 9 (DI or DIO module)
Web application: Config. tab > Measurement settings > Module operation settings
Hardware configurator: Measurement settings > Module operation settings
1 The module numbers that appear depend on the GX/GP module configuration.
Chattering filter for pulse input
Setup Item
On/Off
This filter prevents pulse count errors caused by chattering or noise. By default, the
chattering filter for pulse input is set to On. This is because the pulse input of DI modules
and DI/DO modules may be affected by noise. In normal situations, set the chattering filter
for pulse input to On.
Note
Because the chattering filter for pulse input may not operate properly, update the version of the
DI module or DI/DO module to R1.04.01 or later.
Firmware (Release number 2 and later)"."
Selectable Range or Options
-20.0 to -5.0%
105.0 to 120.0%
Selectable Range or Options
Off, On
See page 5-21 in section 5.1.8, "Updating the
1
Default Value
-10.0
110.0
1
Default Value
On
IM 04L51B01-01EN
1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gx10Gp10Gp20

Table of Contents