IM 04L51B01-01EN
Type
Set the event conditions for executing the action.
Event Type
Description
Internal switch
Select the internal switch number.
Remote
Select the DI channel number of the remote control input.
You cannot set this on a DI of a PID control module.
Relay
Select the DO channel number.
You cannot set this on a DO of a PID control module with the type set to
Contact output within module.
Alarm - I/O channel
Set the alarm of an I/O channel
Channels of PID control modules are not included.
Alarm - Math channel
Set the alarm of a math channel
Alarm - Communication
Set the alarm of a communication channel
channel
Any alarm
The change from no active alarms to one or more active alarms is
regarded as an event.
Alarms of PID control modules are also included.
Timer
Select a timer number. Timer timeout.
Match time timer
Select a match time timer number. When the time matches.
User function key
Select the user function key number.
Status
Select the status.
1 Alarms whose Logging is set to Off in the alarm settings are also applicable.
Number
Set a number from the following table depending on the event type.
Event Type
Description
Internal switch
Internal switch number
Relay
Output relay number (DO channel number)
Alarm - I/O channel
I/O channel number
Alarm - Math channel
Math channel number
Alarm - Communication
Communication channel number
channel
Timer
Timer number
Match time timer
Match time timer number
User function key
User function key number

Alarm level

Set the alarm level (1 to 4).
Event details (release number 2 and later)
Set the status.
Detail
Description
Recording
Recording in progress.
Math
Math in progress.
User lock out
User lock out occurring.
Under login
There is a user logged in.
1
Memory/Media error
Internal memory or external media error
1
Measurement error
Measurement error status.
1
Communication error
Communication error status.
1 For details, see page 1-209 in section 1.23.6, "Setting the FAIL Relay and Instrument Information
Output (/FL option)".
Operation mode
Set the edge type for performing actions.
Operation mode
Description
Rising edge
The action is executed when the event changes from off to on.
Falling edge
The action is executed when the event changes from on to off.
Rising / Falling edge
When the event changes from off to on, the action is changed from off to
on. When the event changes from on to off, the action is changed from
on to off.
You can set this on events other than Timer and Match time timer.
Edge
The action is executed when an event occurs.
This applies when the event is set to Timer or Match time timer.
1.19 Configuring the Event Action Function