1.16 Configuring the Report Function (/MT option)
1.16.2
Setting the Channels to Output Reports
Path
Description
1-154
GX/GP: MENU key > Browse tab > Setting > Setting menu Report settings > Report
channel settings
Web application: Config. tab > Report settings > Report channel settings
Hardware configurator: Report settings > Report channel settings
Setup Item
Report channel number
* There are limits to the number of report channels depending on the measurement mode and
scan interval. For details, see "Explanation."
Report channel number
Select the report channel number. The GX/GP generates reports in order by this number.
Report channel
Setup Item
Channel type
1
Channel no
1
Sum scale
1 Appears when the channel type is not set to Off.
Channel type
Set the channel type to assign to the report channel.
Channel no
Set the channel number to assign to the report channel. All channels can be assigned, but
reports are not created for channels set to Skip or Off even if they are assigned.
Sum scale
Set the sum scale to match the unit of the measured values.
Example: If the unit of the measured value is "m
Off: The measured data is summed as-is once per scan interval.
Selectable Range or Options
GX20/GP20: 1 to 60
GX10/GP10: 1 to 50
Selectable Range or Options
I/O channel, Math channel, Communication
channel, Off
Channels that you can set
Off, /s, /min, /h, /day
3
/min," select /min.
Default Value
1
Default Value
—
—
—
IM 04L51B01-01EN