1.13 Configuring the Dual Interval Settings (Release number 4 and later)
1.13.2
Setting the Scan Interval of Each Module
Path
Description
1.13.3

Setting the Recording Conditions

Path
Description
1-138
GX/GP: MENU key > Browse tab > Setting > Setting menu Dual interval settings > Scan
interval > Module scan interval Main Unit or Unit 1 to 6 > Module 0 to 9
Web application: Config. tab > Dual interval settings > Scan interval
Hardware configurator: Dual interval settings > Scan interval
1 The module numbers that appear depend on the GX/GP module configuration.
Module 0 to Module 9
Setup Item
Measurement group number
Measurement group number
Set the scan group with the scan interval that you want the module to run at.
GX/GP: MENU key > Browse tab > Setting > Setting menu Dual interval settings >
Recording settings
Web application: Config. tab > Dual interval settings > Recording settings
Hardware configurator: Dual interval settings > Recording settings
Recording mode
Setup Item
File type
File type
Event data is recorded (fixed).
Event data (Measurement group 1)
Setup Item
Recording interval
Recording mode
Data length
Recording interval
Set the event data recording interval. You cannot choose a recording interval that is shorter
than the scan interval.
Recording mode
Set the mode for recording event data.
Setup Item
Free
Single
Repeat
Selectable Range or Options
Measurement group 1, measurement group 2
Selectable Range or Options
Event
Selectable Range or Options
1ms, 2ms, 5ms, 10ms, 20ms, 50ms, 100ms,
200ms, 500ms, 1s, 2s, 5s, 10s, 15s, 20
s, 30s, 1min, 2min, 5min, 10min, 15min,
20min, 30
min
Free, Single, Repeat
2min, 5min, 10min, 20min, 30min, 1h, 2, h, 3h,
4h, 6h, 8h, 12h, 1day, 2day, 3day, 5day, 7day,
14day, 31day
Description
Records data at all times
Records data when the trigger condition is met
Records data every time the trigger condition is met
1
Default Value
Default Value
Event
Default Value
1s
Free
1h
IM 04L51B01-01EN