Setting The Match Time Timer - YOKOGAWA GX20 User Manual

Smartdac plus paperless recorder
Hide thumbs Also See for GX20:
Table of Contents

Advertisement

1.18 Setting the Timers
Explanation
1.18.2

Setting the Match Time Timer

Path
Description
1-160
1
Reference time
Setup Item
Hour
Minute
1 Appears when the type is set to Absolute timer.
Hour, Minute
Set the reference time for the absolute timer.
Timers
• Relative Timer
The timer is started when the timer is set, and the timer expires every specified interval.
In this mode, the timer stops when a power failure occurs.
Example: Interval: 00:15
The timer expires every 15 minutes.
• Absolute Timer
The timer expires at the times determined by the reference time and the interval. The
reference time is set on the hour (00 to 23).
Example: Reference time: 00:00
Interval: 10 min
The timer expires at 0 hour, 0 hour 10 min, 0 hour 20 min, . . . 23 hour 40 min,
and 23 hour 50 min.
For example, if the timer is set at 9 hour 36 min, the timer expires at 09 hour 40
min,
09 hour 50 min, 10 hour, and so on.
Absolute timer
Set the timer
Ref. time
A
A
A
Timeout
GX/GP: MENU key > Browse tab > Setting > Setting menu Timer settings > Match time
timer Match time timer 1 to 12
Web application: Config. tab > Timer settings > Match time timer
Hardware configurator: Timer settings > Match time timer
Type
Setup Item
Type
Type
Set the kind of match time timer.
Options
Off
Day
Week
Month
Year
Selectable Range or Options
0 to 23
0 to 59
Relative timer
Set the timer
Reset the timer
Time
A
A: Interval
Selectable Range or Options
Off, Day, Week, Month, Year
Description
Disables the function.
Set the time match condition of a day.
Set the time match condition of a week.
Set the time match condition of a month.
Set the time match condition of a year.
Default Value
0
0
Time
B
B
B: Interval
Default Value
Off
IM 04L51B01-01EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gx10Gp10Gp20

Table of Contents