1.13 Configuring the Dual Interval Settings (Release number 4 and later)
1.13.4

Configuring Recording Channels

Path
Description
1-140
GX/GP: MENU key > Browse tab > Setting > Setting menu Dual interval settings >
Recording channel settings
Web application: Config. tab > Dual interval settings > Recording channel settings
Hardware configurator: Dual interval settings > Recording channel settings
Measurement group 1
Setup Item
Event data
Event data
Set the channels for recording event data with measurement group 1. Channels that you can
specify are displayed.
If you specify more than the number of recordable channels, the recording interval will be
increased.
Measurement group 2
Setup Item
Event data
Event data
Set the channels for recording event data with measurement group 2. Channels that you can
specify are displayed.
If you specify more than the number of recordable channels, the recording interval will be
increased.
Manual sample
Setup Item
Manual sample
Manual sample
Set the channels for recording manual sampled data. Channels that you can specify are
displayed.
Number of Recording Channels
Model
GX10/GP10
GX20-1/GP20-1
GX20-2/GP20-2
Selectable Range or Options
AI, DI, pulse input, AO, DO, math,
communication channels
Selectable Range or Options
AI, DI, pulse input, AO, DO, math,
communication channels
Selectable Range or Options
AI, DI, pulse input, AO, DO, math,
communication channels
Maximum number of channels
50
50
100
Default Value
Default Value
Default Value