1.11.5
Setting the Noise Rejection (High-speed AI, PID control module) (Release
number 4 and later)
Path
Description
IM 04L51B01-01EN
1.11 Setting Measurement Conditions (Scan interval, A/D integrate, etc.)
GX/GP: MENU key > Browse tab > Setting > Setting menu Measurement settings >
Select unit Main unit or Unit1 to 6 > Module 0 to 9
Web application: Config. tab > Measurement settings > Module operation settings
Hardware configurator: Measurement settings > Module operation settings
1 The module numbers that appear depend on the GX/GP module configuration.
Noise rejection
Setup Item
Noise rejection
2 Common appears when the scan interval is 100 ms or longer.
3 Depends on the scan interval. Refer to the noise rejection modes that are available depending
on the scan interval.
Noise rejection
Set the noise rejection. The available options appear depending on the scan interval setting.
If you are using the 24 VDC power supply on models with the 24 VDC/AC power supply (/P1
option), the noise rejection is fixed to 50Hz.
If the 12 VDC power supply (GP10-1J2W) is in use, the noise rejection is fixed to 50Hz.
For PID control modules, the noise rejection is fixed to Common.
Options
Description
Auto
The GX/GP automatically detects the power supply frequency and rejects
50 Hz noise for 50 Hz or 60 Hz noise for 60 Hz. However, noise is not
rejected if the scan interval is set to 1 ms, 2 ms, 5 ms, or 10 ms.
50Hz
50 Hz noise is rejected.
60Hz
60 Hz noise is rejected.
Common
50 Hz and 60 Hz noise is rejected simultaneously.
Noise rejection modes that are available depending on the scan interval
Scan interval
Available noise rejection modes
1ms
Auto
2ms
Auto
5ms
Auto
10ms
Auto
20ms
Auto
50Hz
60Hz
50ms
Auto
50Hz
60Hz
100 ms to 5 s
Common
Selectable Range or Options
2
Auto, 50Hz, 60Hz, Common
Default Value
Auto
Auto
Auto
Auto
Auto
Auto
1
Default Value
3
Filter
None
None
None
None
50 Hz or 60 Hz auto selection
50Hz
60Hz
50 Hz or 60 Hz auto selection
50Hz
60Hz
50 Hz and 60 Hz simultaneous
rejection