1.13 Configuring the Dual Interval Settings (Release
number 4 and later)
1.13.1

Setting the Scan Interval

Path
Description
IM 04L51B01-01EN
These settings apply when the measurement mode is set to Dual interval.
GX/GP: MENU key > Browse tab > Setting > Setting menu Dual interval settings > Scan
interval
Web application: Config. tab > Dual interval settings > Scan interval
Hardware configurator: Dual interval > Scan interval
Scan interval
Setup Item
Measurement group 1
Measurement group 2
1 You cannot specify this value when an electromagnetic relay type module is used in the same
measurement group.
2 2s when an electromagnetic relay type module is used in the same measurement group.
3 You cannot specify this value when a low withstand voltage relay type module is used in the
same measurement group.
4 You can specify this value when only a high-speed universal type module is in use. However,
can not settings 1 ms and 2 ms for GX10, GP10, GX20-1, GP20-1.
Measurement group 1
Set the scan interval of measurement group 1. You can select from the scan intervals
available depending on the installed module.
Measurement group 2
Set the scan interval of measurement group 2. You can select from the scan intervals
available depending on the installed module.
Note
You cannot set the scan intervals of measurement group 1 and measurement group 2 to the
same value.
The selectable range of scan intervals of each measurement group varies depending on the
module assigned to the group. The longest scan interval among the assigned modules becomes
the shortest scan interval that can be specified.
Master Scan Interval
Setup Item
Measurement group number
Measurement group number
Set the measurement group number with the scan interval that you want to use as the
master scan interval.
Selectable Range or Options
4
4
4
4
1ms
, 2ms
, 5ms
, 10ms
, 20ms
1, 3
1, 3
1
100ms
, 200ms
, 500ms
, 1s, 2s, 5s
1, 3
1, 3
1
100ms
, 200ms
, 500ms
, 1s, 2s, 5s
Selectable Range or Options
Measurement group 1, measurement group 2
Default Value
4
4
2
, 50ms
,
1s
2s
Default Value
Measurement
group 1
1-137
1
2
3
4
5
App
Index