1.19 Configuring The Event Action Function; Setting Event Action Numbers And Actions - YOKOGAWA GX20 User Manual

Smartdac plus paperless recorder
Hide thumbs Also See for GX20:
Table of Contents

Advertisement

1.19 Configuring the Event Action Function
1.19.1
Setting Event Action Numbers and Actions
Path
Description
1-162
The event action function is used to execute a specified action on the basis of events that
occur. The settings explained here are also used to configure the remote control function.
Select an event action number, and set event action to On.
Set the even type and event-specific conditions.
Then, set the action for the event and the action conditions.
GX/GP: MENU key > Browse tab > Setting > Setting menu Event action
Web application: Config. tab > Event action > Event action number (display example:
1-20)
Hardware configurator: Event action > Event action number (display example: 1-20)
Setup Item
Event action number
Event action number
Select the event action number to assign an event action.
Event action
Setup Item
On/Off
On/Off
Select On to use the event action function.
1
Event
Setup Item
Type
2
Number
3
Alarm level
6
Event details
Operation mode
1 Appears when Event action is set to On.
2 Does not appear when Type is set to Any alarm.
3 Appears when the Type is to Alarm - I/O channel, Alarm - Math channel, or Alarm -
Communication channel.
4 Appears when the operation mode of the DI module is set to Remote.
5 Appears when the event is set to Timer or Match time timer.
6 Appears when the type is set to Status.
7 Appears for the advanced security function (/AS option).
8 Release number 2 and later.
Selectable Range or Options
1 to 50
Selectable Range or Options
Off, On
Selectable Range or Options
4
Internal switch, Remote,
Relay, Alarm - IO channel,
Alarm - Math channel, Alarm - Communication
channel, Any alarm, Timer, Match time timer, User
8
8
function key
, Status
IO channel, Math channel, Communication channel,
Internal switch, Timer, Match time timer, User function
key, Relay, Remote
1 to 4
Recording, Math, User lock out
Media error, Measurement error, Communication error
Rising edge, Falling edge, Rising/Falling edge, Edge
Default Value
1
Default Value
Off
Default Value
Internal switch
1
1
7
7
, Under login
, Memory/
Recording
5
Rising edge
IM 04L51B01-01EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gx10Gp10Gp20

Table of Contents