Reference Manual
00809-0300-4101, Rev BB
Note
Security jumper must be in the off position for the LOI to operate. The password appears
after the LOI is activated using the local configuration buttons.
2.6.9

Simulation

The Rosemount 2051 has a simulation jumper located on the electronics board (or optional
LCD display) that must be set to the ON position in order to simulate.
With the AI block simulation enabled, the actual measurement value has no impact on the
OUT value or the status.
Simulation configuration using Class 2 Master
1. Set the simulation jumper to on.
2. To enable simulation, select the following in Basic Setup >> Simulation:
a. Select Enabled.
b. Enter Simulation Value.
c. Select Simulation Status.
d. Select Transfer.
3. To disable simulation, select the following in Basic Setup >> Simulation:
a. Select Disabled.
b. Select Transfer.
4. Set the simulation jumper to off.
Configuration
Configuration
November 2016
15