Specifications and Reference Data
November 2016
Models
Standard
2051T
±0.065% of span
For spans less than 10:1, accuracy =
Ranges 1–4
URL
±
0.0075
-------------
Span
±0.075% of span
For spans less than 10:1, accuracy =
Range 5
URL
±
0.0075
-------------
Span
2051L
±0.075% of span
For spans less than 10:1, accuracy =
Ranges 2–4
±
0.025
+
0.005
1.
Not available with output code W.
2.
For protocol code F, accuracy specification is for spans less than 7:1.
A.1.3 Flow performance
Flow reference accuracy
Rosemount 2051CFA Annubar Flowmeter
Ranges 2–3
Rosemount 2051CFC_A Compact Annubar Flowmeter — Annubar option A
Standard
Ranges 2–3
Calibrated
Rosemount 2051CFC Compact Orifice Flowmeter — conditioning option C
β = 0.4
Ranges 2–3
β = 0.65
Rosemount 2051CFC Compact Orifice Flowmeter — orifice type option P
β =0.4
Ranges 2–3
β =0.65
Rosemount 2051CFP Integral Orifice Flowmeter
Bore < 0.1
0.1 < Bore < 0.2
Ranges 2–3
0.2 < Bore < 0.6
0.6 < Bore < 0.8
1.
For smaller line sizes, see Rosemount Compact Orifice.
62
% of span
% of span
URL
% of span
-------------
Span
±2.00% of flow rate at 5:1 flow turndown
±2.60% of flow rate at 5:1 flow turndown
±2.30% of flow rate at 5:1 flow turndown
±2.25% of flow rate at 5:1 flow turndown
±2.45% of flow rate at 5:1 flow turndown
±2.50% of flow rate at 5:1 flow turndown
±2.50% of flow rate at 5:1 flow turndown
±3.10% of flow rate at 5:1 flow turndown
±2.75% of flow rate at 5:1 flow turndown
±2.25% of flow rate at 5:1 flow turndown
±3.00% of flow rate at 5:1 flow turndown
High performance option, P8
High accuracy option, P8
±0.05% of span
For spans less than 10:1
Ranges 1–4
±
0.0075
N/A
N/A
N/A
N/A
(1)
Reference Manual
00809-0300-4101, Rev BB
(1)
(2)
, accuracy =
URL
% of span
-------------
Span
Specifications and Reference Data