Product Certifications
November 2016
E6
Canada Explosion-Proof, Dust Ignition Proof
Certificate: 2041384
Standards: CAN/CSA C22.2 No. 0-10,
CSA Std C22.2 No. 25-1966,
CSA Std C22.2 No. 30-M1986,
CAN/CSA-C22.2 No. 94-M91,
CSA Std C22.2 No.142-M1987,
CAN/CSA-C22.2 No.157-92, CSA Std
C22.2 No. 213-M1987,
CAN/CSA-E60079-0:07,
CAN/CSA-E60079-1:07,
CAN/CSA-E60079-11-02,
CAN/CSA-C22.2 No.60529:05,
ANSI/ISA-12.27.01–2003
Markings: Explosion-Proof for Class I, Divisions 1,
Groups B, C, and D. Dust-Ignition Proof for
Class II and Class III, Division 1, Groups E,
F, and G. Suitable for Class I, Division 2;
Groups A, B, C, and D for indoor and
outdoor hazardous locations. Class I Zone
1 Ex d IIC T5. Enclosure type 4X, factory
sealed. Single Seal.
I6
Canada Intrinsic Safety
Certificate: 2041384
Standards: CSA Std. C22.2 No. 142 - M1987,
CSA Std.C22.2 No. 213 - M1987,
CSA Std. C22.2 No.157 - 92,
CSA Std. C22.2 No. 213 - M1987,
ANSI/ISA 12.27.01 – 2003,
CAN/CSA-E60079-0:07,
CAN/CSA-E60079-11:02
Markings: Intrinsically safe for Class I, Division 1,
Groups A,B, C, and D when connected in
accordance with Rosemount drawing
02051-1008. Ex ia IIC T3C. Single Seal.
Enclosure Type 4X.
B.4 Europe
E1
ATEX Flameproof
Certificate: KEMA 08ATEX0090X
Standards: EN 60079-0:2012 + A11:2013, EN
60079-1:2014, EN 60079-26:2015
Markings:
II 1/2 G Ex db IIC T6
(–60 °C
T
T4/T5 (-60 °C
Table B-1. Process Connection Temperature
Temperature
class
temperature
T6
–60 °C to +70 °C
T5
–60 °C to +80 °C
T4
–60 °C to +120 °C –60 °C to +80 °C
132
+70°C);
a
T
+80 °C)
a
Process
Ambient
Temperature
–60 °C to +70 °C
–60 °C to +80 °C
Special Conditions for Safe Use (X):
1. Appropriate cable, glands and plugs need to be
suitable for a temperature of 5 °C greater than
maximum specified temperature for location where
installed.
2. Non- standard paint options may cause risk from
electrostatic discharge. Avoid installations that could
cause electrostatic build-up on painted surfaces, and
only clean the painted surfaces with a damp cloth. If
paint is ordered through a special option code,
contact the manufacturer for more information.
3. 2.3.The device contains a thin wall diaphragm less
than 1 mm thickness that forms a boundary between
zone 0 (process connection) and zone 1 (all other
parts of the equipment). The model code and
datasheet are to be consulted for details of the
diaphragm material. Installation, maintenance and
use shall take into account the environmental
conditions to which the diaphragm shall be subjected.
The manufacturer's instructions for installation and
maintenance shall be followed in detail to assure
I1
ATEX Intrinsic Safety
Certificate: Baseefa08ATEX0129X
Standards: EN60079-0:2012, EN60079-11:2012
Markings:
II 1 G Ex ia IIC T4 Ga
(–60 °C
Table B-2. Input Parameters
HART
Parameter
Voltage U
i
Current l
200 mA
i
Power P
1.0 W
i
0.012 μF
Capacitance C
i
Inductance L
0 mH
i
Special Condition for Safe Use (X):
1. If the equipment is fitted with an optional 90 V
transient suppressor, it is incapable of withstanding
the 500 V isolation from earth test and this must be
taken into account during installation.
2. The enclosure may be made of aluminum alloy and
given a protective polyurethane paint finish; however
care should be taken to protect it from impact and
abrasion when located in Zone 0.
IA
ATEX FISCO
Certificate: Baseefa08ATEX0129X
Standards: EN60079-0:2012, EN60079-11:2012
Markings:
II 1 G Ex ia IIC T4 Ga
(–60 °C
Reference Manual
00809-0300-4101, Rev BB
T
+70 °C)
a
Fieldbus/PROFIBUS
30 V
30 V
300 mA
1.3 W
0 μF
0 mH
T
+60 °C)
a
Product Certifications