Japan; Technical Regulations Customs Union (Eac); B.10Combinations - Emerson Rosemount 2051 Reference Manual

Pressure transmitter with profibus pa protocol
Hide thumbs Also See for Rosemount 2051:
Table of Contents

Advertisement

Product Certifications
November 2016
The enclosure may be made of aluminum alloy
and given a protective polyurethane paint finish;
however, care should be taken to protect it from
impact or abrasion if located in Zone 0.
2. The relation between T code and ambient
temperature range is:
Model
T code Temperature range
HART, Fieldbus,
PROFIBUS, and
Low Power
3. Intrinsically safe parameters:
HART
Parameter
Voltage U
30 V
i
Current l
200 mA
i
Power P
1 W
i
0.012 μF
Capacitance C
i
Inductance L
0 mH
i
Note 1: FISCO parameters comply with the
requirements for FISCO field devices in
GB3836.19-2010.
Note 2: [For Flowmeters] When Rosemount 644
Temperature Transmitter is used, the transmitter
should be used with Ex-certified associated apparatus
to establish explosion protection system that can be
used in explosive gas atmospheres. Wiring and
terminals should comply with the instruction manual
of both Rosemount 644 and associated apparatus.
The cables between Rosemount 644 and associated
apparatus should be shielded cables (the cables must
have insulated shield). The shielded cable has to be
grounded reliably in a non-hazardous area.
4. The product should be used with Ex-certified
associated apparatus to establish explosion
protection system that can be used in explosive gas
atmospheres. Wiring and terminals should comply
with the instruction manual of the product and
associated apparatus.
5. The cables between this product and associated
apparatus should be shielded cables (the cables must
have insulated shield). The shielded cable has to be
grounded reliably in a non-hazardous area.
6. End users are not permitted to change any internal
components, and needs to settle the problem in
conjunction with the manufacturer to avoid damage
to the product.
7. During installation, use and maintenance of this
product, observe the following standards:
GB3836.13-2013, GB3836.15-2000,
GB3836.16-2006, GB3836.18-2010, GB50257-2014.
136
–60 °C ≤ T
≤ +70 °C
T4
a
Fieldbus/
FISCO
PROFIBUS
30 V
17.5 V
300 mA
380 mA
1.3 W
5.32 W
0 μF
0 nF
0 μF
0 mH
B.8 Japan
E4
Japan Flameproof
Certificate: TC20598, TC20599, TC20602, TC20603
[HART]; TC20600, TC20601, TC20604,
TC20605 [Fieldbus]
Markings: Ex d IIC T5
B.9 Technical Regulations Customs
Union (EAC)
EM EAC Flameproof
Certificate: RU C-US.GB05.B.01199
Markings: Ga/Gb Ex d IIC T5/T6 X,
T5(–50 °C
T6(–50 °C
Special Condition for Safe Use (X):
1. See certificate for special conditions.
IM
EAC Intrinsically Safe
Certificate: RU C-US.GB05.B.01199
Markings: 0Ex ia IIC T4 Ga X (–60 °C
Special Condition for Safe Use (X):
1. See certificate for special conditions.
B.10 Combinations
K1
Combination of E1, I1, N1, and ND
K2
Combination of E2 and I2
K5
Combination of E5 and I5
K6
Combination of E6 and I6
K7
Combination of E7, I7, N7 and IECEx Dust
IECEx Dust
Certificate: IECExBAS08.0058X
Standards: IEC60079-0:2011, IEC60079-15:2010
Markings: Ex nA IIIC T95 °C T
(–20 °C
Special Condition for Safe Use (X):
1. If the equipment is fitted with an optional 90 V
transient suppressor, it is incapable of withstanding a
500 V isolation from earth test and this must be taken
into account during installation.
KA
Combination of E1, I1, and K6
KB
Combination of K5 and K6
KC
Combination of E1, I1, and K5
KD
Combination of K1, K5, and K6
KM Combination of EM and IM
Reference Manual
00809-0300-4101, Rev BB
T
+80 °C),
a
T
+65 °C)
a
T
+70 °C)
a
105 °C Da
500
T
+85 °C)
a
Product Certifications