Reference Manual Table of Contents 00809-0300-4101, Rev BB November 2016 Contents 1Section 1: Introduction Using this manual............1 Models covered .
Page 4
Reference Manual Table of Contents 00809-0300-4101, Rev BB November 2016 Installation procedures ..........18 3.4.1 Mount the transmitter .
Page 5
Reference Manual Table of Contents 00809-0300-4101, Rev BB November 2016 5.5.1 LOI ............48 5.5.2 Class 2 Master .
Page 6
Reference Manual Table of Contents 00809-0300-4101, Rev BB November 2016 Functional specifications ..........64 A.2.1 Range and sensor limits.
Page 7
Reference Manual Table of Contents 00809-0300-4101, Rev BB November 2016 A.4.10Transient protection ..........73 A.4.11Bolts for flanges and adapters .
Page 8
Reference Manual Table of Contents 00809-0300-4101, Rev BB November 2016 viii Table of Contents...
Page 9
The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings. For information on Rosemount nuclear-qualified products, contact your local Emerson Process Management Sales Representative. Explosions could result in death or serious injury.
Page 10
Reference Manual Title Page 00809-0300-4101, Rev BB November 2016 Title Page...
Reference Manual Introduction 00809-0300-4101, Rev BB November 2016 Section 1 Introduction Using this manual The sections in this manual provide information on installing, operating, and maintaining ™ ® the Rosemount 2051 Pressure Transmitter with PROFIBUS PA Protocol. The sections are organized as follows: Section 2: Configuration provides instruction on commissioning and operating Rosemount...
Process Management capacitance sensor technology for DP and GP measurements. Piezoresistive sensor technology is utilized in the Rosemount 2051T. The major components of the Rosemount 2051 are the sensor module and the electronics housing. The sensor module contains the oil filled sensor system (isolating diaphragms, oil fill system, and sensor) and the sensor electronics.
Master from seeing a jump in output without a status change. Setting the blocks OOS and back into Auto might be done automatically using the Class 2 Master when using the Rosemount 2051 DD or DTM, if no additional action is required when configuring the device. Verify the block mode is set back to Auto.
2.5.1 Assign address The Rosemount 2051 is shipped with a temporary address of 126. This must be changed to a unique value between 0 and 125 in order to establish communication with the Class 1 Master. Usually, addresses 0–2 are reserved for masters, therefore transmitter addresses between 3 and 125 are recommended for the device.
Page 18
Reference Manual Configuration 00809-0300-4101, Rev BB November 2016 Figure 2-1. LOI Menu ENTER into menu 1. ADDRESS 1 - 126 2. CALIBRATION ZERO LOWER SENSOR 3. UNITS PRESSURE UPPER SENSOR FLOW 4. DAMPING RESET FACTORY LEVEL 5. DISPLAY TEMPERATURE 6. IDENTIFICATION # 7.
From the Basic Setup >> Units >> Output Signal (Analog Input Block) >> Linearization Type dropdown, select No Linearization. Detailed setup tasks The following tasks explain how to configure the Rosemount 2051 for Flow or Level measurement and how to configure additional parameters found in the device. 2.6.1 Flow configuration To configure the Rosemount 2051 for flow measurement with the LOI, select UNITS >>...
2.6.2 Square Root of DP Configuration The Rosemount 2051 has two Pressure output settings: Linear and Square Root. Activate the square root output option to make output proportional to flow. To configure the transmitter to output square root of differential pressure, a Class 2 Master must be used.
From the Basic Setup >> Units >> Output Signal (Analog Input Block) >> Linearization Type dropdown, select Square Root. 2.6.3 Level configuration To configure the Rosemount 2051 for Level measurement with the LOI, select UNITS >> LEVEL. When configuring level units, the following parameters are set: Measurement type: Level ...
Page 22
Reference Manual Configuration 00809-0300-4101, Rev BB November 2016 Class 2 Master To configure the transmitter for a level application, use the level output in the Transducer Block. See Level configuration using Class 2 Master. Level configuration using Class 2 Master 1.
2.6.4 Damping User-selected damping will affect the transmitters ability to respond to changes in the applied process. The Rosemount 2051 has a default damping value of 0.0 seconds applied in the AI Block. Damping can be set using, LOI – see...
2.6.7 Security The Rosemount 2051 has a hierarchy of security features. The security jumper on the electronics board (or optional LCD display) provides the highest level of security. With the jumper in the ON position, all writes to the transmitter will be disabled (including writes from the LOI or a Class 2 Master).
2.6.9 Simulation The Rosemount 2051 has a simulation jumper located on the electronics board (or optional LCD display) that must be set to the ON position in order to simulate. With the AI block simulation enabled, the actual measurement value has no impact on the OUT value or the status.
Reference Manual Hardware Installation 00809-0300-4101, Rev BB November 2016 Important Install the enclosed pipe plug (found in the box) in unused conduit opening. Engage a minimum of five threads to comply with explosion-proof requirements. See “Conduit entry threads” on page 19 for additional requirements.
Page 29
Always ensure a proper seal by installing electronics housing cover(s) so that metal contacts metal. Use Rosemount O-rings. Mounting brackets Rosemount 2051 may be panel-mounted or pipe-mounted through an optional mounting bracket. Refer to Table 3-1 for the complete offering and see...
Page 31
2.81 (71) Dimensions are in inches (millimeters). Flange bolts The Rosemount 2051 can be shipped with a coplanar flange or a traditional flange installed with four 1.75-inch flange bolts. Mounting bolts and bolting configurations for the coplanar ™ and traditional flanges can be found on page 22.
Page 32
Hardware Installation 00809-0300-4101, Rev BB November 2016 Bolt installation Only use bolts supplied with the Rosemount 2051 or sold by Emerson Process Management as spare parts for the Rosemount 2051 Transmitter. Use the following bolt installation procedure: 1. Finger-tighten the bolts.
Reference Manual Hardware Installation 00809-0300-4101, Rev BB November 2016 Figure 3-7. Mounting Bolts and Bolt Configurations for Coplanar Flange Transmitter with Transmitter with flange adapters and flange bolts flange/adapter bolts 1.75 (44) × 4 2.88 (73) × 4 Dimensions are in inches (millimeters). Description Size in.
Page 34
Reference Manual Hardware Installation 00809-0300-4101, Rev BB November 2016 Steam flow measurement 1. Place taps to the side of the line. 2. Mount the transmitter below the taps to ensure that the impulse piping will stay filled with condensate. 3. In steam service above 250 °F (121 °C), fill impulse lines with water to prevent steam from contacting the transmitter directly and to ensure accurate measurement start-up.
Reference Manual Hardware Installation 00809-0300-4101, Rev BB November 2016 Keep corrosive or hot (above 250 °F [121 °C]) process material out of direct contact with the sensor module and flanges. Prevent sediment deposits in the impulse piping. Maintain equal leg of head pressure on both legs of the impulse piping. ...
Reference Manual Hardware Installation 00809-0300-4101, Rev BB November 2016 O-rings The two styles of Rosemount flange adapters (Rosemount 1151 and Rosemount 3051S/3051/2051) each require a unique O-ring. Use only the O-ring designed for the corresponding flange adapter. Failure to install proper flange adapter O-rings may cause process leaks, which can result in death or serious injury.
3.5.1 Rosemount 305 Integral Manifold installation procedure To install a Rosemount 305 Integral Manifold to a Rosemount 2051 Transmitter: 1. Inspect the PTFE sensor module O-rings. Undamaged O-rings may be reused. If the O-rings are damaged (if they have nicks or cuts, for example), replace with O-rings designed for Rosemount transmitter.
3.5.3 Rosemount 304 Conventional Manifold installation procedure To install a Rosemount 304 Conventional Manifold to a Rosemount 2051 Transmitter: 1. Align the conventional manifold with the transmitter flange. Use the four manifold bolts for alignment. 2. Finger tighten the bolts, then tighten the bolts incrementally in a cross pattern to final torque value.
Page 39
Reference Manual Hardware Installation 00809-0300-4101, Rev BB November 2016 1. To zero trim the transmitter, close the isolate valve on the low side (downstream) side of the transmitter. Drain/Vent Drain/Vent valve valve Equalize (closed) Isolate Isolate (open) (closed) Process 2. Open the equalize valve to equalize the pressure on both sides of the transmitter.
Page 40
Reference Manual Hardware Installation 00809-0300-4101, Rev BB November 2016 5-valve natural gas manifold Performing zero trim at static line pressure 5-valve natural gas configurations shown: In normal operation, the two isolate (block) valves between the process ports and transmitter will be open, and the equalize valves will be closed.
Page 41
Reference Manual Hardware Installation 00809-0300-4101, Rev BB November 2016 4. After performing a zero trim on the transmitter, close the equalize valve on the low pressure (downstream) side of the transmitter. (Plugged) (Plugged) Equalize Equalize (open) (closed) Isolate Isolate (open) (closed) Process Drain vent...
Page 42
Reference Manual Hardware Installation 00809-0300-4101, Rev BB November 2016 1. To isolate the transmitter, close the isolate valve. Transmitter Vent (closed) Isolate Process (closed) 2. To bring the transmitter to atmospheric pressure, Transmitter open the vent valve or bleed screw. Note Vent (open)
Reference Manual Hardware Installation 00809-0300-4101, Rev BB November 2016 Adjusting valve packing Over time, the packing material inside a Rosemount manifold may require adjustment in order to continue to provide proper pressure retention. Not all Rosemount manifolds have this adjustment capability. The Rosemount manifold model number will indicate what type of stem seal or packing material has been used.
Reference Manual Hardware Installation 00809-0300-4101, Rev BB November 2016 3.6.1 Open vessels A pressure transmitter mounted near a tank bottom measures the pressure of the liquid above. Make a connection to the high pressure side of the transmitter, and vent the low pressure side to the atmosphere.
Page 45
Reference Manual Hardware Installation 00809-0300-4101, Rev BB November 2016 Wet leg condition Condensation of the gas above the liquid slowly causes the low side of the transmitter piping to fill with liquid. The pipe is purposely filled with a convenient reference fluid to eliminate this potential error.
Page 46
Reference Manual Hardware Installation 00809-0300-4101, Rev BB November 2016 Bubbler system in open vessel A bubbler system that has a top-mounted pressure transmitter can be used in open vessels. This system consists of an air supply, pressure regulator, constant flow meter, pressure transmitter, and a tube that extends down into the vessel.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock. LCD display Transmitters ordered with the LCD display option (M5) are shipped with the display installed. Installing the display on an existing Rosemount 2051 requires a small instrument screwdriver. Electrical Installation...
4.5.1 Security (write protect) There are four security methods with the Rosemount 2051 Transmitter: 1. Security jumper: prevents all writes to transmitter configuration including use of the LOI. 2. Software Write Protection: prevents all writes to the transmitter configuration using a Class 2 Master.
OFF configuration. 4.5.2 Simulate The Rosemount 2051 has a simulate jumper located on the electronics board (or optional LCD display) that must be set to the ON position in order to activate simulate mode using a Class 2 Master. Section 2: Configuration for details on simulate mode.
2. Connect the power leads to the terminals indicated on the terminal block label. Figure 4-4 Rosemount 2051 PROFIBUS terminal block. 3. Tighten terminal screws to ensure full contact with the terminal block screw and washer. When using a direct wiring method, wrap wire clockwise to ensure it is in place when tightening the terminal block screw.
Reference Manual Electrical Installation 00809-0300-4101, Rev BB November 2016 Figure 4-4. Rosemount 2051 PROFIBUS Terminal Block A. Terminals B. Ground terminal Figure 4-5. Basic PROFIBUS PA System Configuration A. 6234 ft (1900 m) max (depending upon cable characteristics) F. Trunk B.
Reference Manual Electrical Installation 00809-0300-4101, Rev BB November 2016 4.6.3 Signal wiring grounding Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment. Grounding terminations are provided on the outside of the electronics housing and inside the terminal compartment.
The transient protection terminal block can be ordered as an installed option (Option Code T1 in the transmitter model number) or as a spare part to retrofit existing Rosemount 2051 Transmitters in the field. See “Other spare parts”...
Reference Manual Electrical Installation 00809-0300-4101, Rev BB November 2016 4.6.5 Grounding Use the following techniques to properly ground the transmitter signal wiring and case: Signal wiring Do not run signal wiring in conduit or open trays with power wiring or near heavy electrical equipment.
– in order to optimize performance over a specific pressure range. Note The Rosemount 2051 has been carefully calibrated at the factory. Trimming adjusts the position of the factory characterization curve. It is possible to degrade performance of the transmitter if any trim is done improperly or with inaccurate equipment.
Reference Manual Calibration 00809-0300-4101, Rev BB November 2016 Determining calibration frequency Calibration frequency can vary greatly depending on the application, performance requirements, and process conditions. Use the following procedure to determine calibration frequency that meets the needs of your application: 1.
Reference Manual Calibration 00809-0300-4101, Rev BB November 2016 Zero trim Note The transmitter PV at zero pressure must be within 10% upper sensor limit (USL) of zero in order to calibrate using the zero trim function. 5.5.1 1. Enter Calibration >> Zero. a.
Reference Manual Calibration 00809-0300-4101, Rev BB November 2016 5.6.2 Class 2 Master 1. To set the Transducer Block to Out of Service, select the following: a. From the Basic Setup >> Mode >> Transducer Block >> Target Mode dropdown, select Out of Service.
Applying high static pressure to Rosemount 2051 Range 4 and 5 Pressure Transmitters causes a systematic shift in the output. This shift is linear with static pressure; correct it by performing the “Sensor trim”...
Diagnostics identification and recommended action The Rosemount 2051 PROFIBUS device diagnostics can be used to warn a user about a potential transmitter error. There is a transmitter error if the Output Status reads anything but Good or Good - Function Check, or the LCD display reads SNSR or ELECT. Use...
Reference Manual Troubleshooting 00809-0300-4101, Rev BB November 2016 How to identify Diagnostics What to do Class 1 or 2 condition Class 2 Master Master Physical block Diagnostics Primary Temperature diagnostic Recommended action condition value status status extension 1. Verify the sensor Module temperature is between Temperature...
Reference Manual Troubleshooting 00809-0300-4101, Rev BB November 2016 Alert messages and fail safe type selection Table 6-5 defines the output status and LCD display messages that will be driven by a diagnostic condition. This table can be used to determine what type of fail safe value setting is preferred.
Reference Manual Troubleshooting 00809-0300-4101, Rev BB November 2016 Disassembly procedures Do not remove the instrument cover in explosive atmospheres when the circuit is live. 6.7.1 Remove from service Follow these steps: 1. Follow all plant safety rules and procedures. 2. Isolate and vent the process from the transmitter before removing the transmitter from service.
Reference Manual Troubleshooting 00809-0300-4101, Rev BB November 2016 4. Using the two captive screws, slowly pull the electronics board out of the housing. The sensor module ribbon cable holds the electronics board to the housing. Disengage the ribbon cable by pushing the connector release. 6.7.4 Remove the sensor module from the electronics housing 1.
Reference Manual Troubleshooting 00809-0300-4101, Rev BB November 2016 6.8.1 Attach the electronics board 1. Remove the cable connector from its position inside of the internal black cap and attach it to the electronics board. 2. Using the two captive screws as handles, insert the electronics board into the housing. Make sure the posts from the electronics housing properly engage the receptacles on the electronics board.
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Appendix A Specifications and Reference Data Performance specifications ..........page 61 Functional specifications .
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Models Standard High performance option, P8 2051T High accuracy option, P8 ±0.065% of span ±0.05% of span For spans less than 10:1 , accuracy = For spans less than 10:1, accuracy = Ranges 1–4 Ranges 1–4 ...
Line pressure effect per 1000 psi (6,9 MPa) Ambient temperature effect per 50 °F (28 °C) For line pressures above 2000 psi (13,7 MPa) and Ranges Models Ambient temperature effect 4–5, see Rosemount 2051 Reference Manual for HART, 2051C, 2051CF Rosemount 2051...
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Mounting position effects Power supply effect Less than ±0.005% of calibrated span per volt. Models Mounting position effects Electromagnetic compatibility (EMC) Zero shifts up to ±1.25 inH O (3,1 mbar), 2051C Meets all relevant requirements of EN 61326 and which can be calibrated out.
November 2016 00809-0300-4101, Rev BB A.2.2 Service Rosemount2051 with Selectable HART The Rosemount 2051 with Selectable HART comes with Liquid, gas, and vapor applications Selectable HART Revisions. Digital communications based A.2.3 4–20 mA HART (output code A) on HART Revision 5 (default) or Revision 7 (option code HR7) Protocol can be selected.
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Fieldbus parameters Arithmetic block OUNDATION The arithmetic (ARTH) function block provides the Schedule entries 7 (max.) ability to configure a range extension function for a Links 25 (max.) primary input. It can also be used to compute nine different arithmetic functions including flow with Virtual communications relationships (VCR) 20 (max.) partial density compensation, electronic remote seals,...
Output Protocol. IEC 62591 (WirelessHART), 2.4 GHz DSSS Rosemount 2051 with Selectable HART Wireless radio (internal antenna, WP5 option) The Rosemount 2051 with Selectable HART comes with Frequency: 2.400–2.485 GHz Selectable HART Revisions. Digital communications based Channels: 15 ...
With Wireless output: –40 °F to 185 °F (–40 °C to 85 °C) Range 4: 6,000 psi (413,7 bar) Rosemount 2051 LCD display may not be readable and LCD display Range 5: 15,000 psi (1034,2 bar) °F (–30 °C).
A.3.1 Material selection Rosemount 2051 with selectable HART Analog output response to a step input change is Emerson provides a variety of Rosemount product with user-enterable from 0 to 60 seconds for one time various product options and configurations including constant.
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB A.3.2 Electrical connections Process isolating diaphragms 316L SST, Alloy C-276, or Tantalum –14 NPT, G , and M20 1.5 conduit A.3.5 Rosemount 2051T process wetted parts A.3.3 Process connections Process connections Rosemount 2051C –18 NPT on 2...
@ 0 °C and more kg/cm O @ 60 °F Refer to the Rosemount 2051 Configuration Data Sheet mHg @ 0 °C O @ 4 °C the Rosemount 2051 Wireless Configuration Data Sheet. O @ 4 °C mHg @ 0 °C...
For use with the traditional flange option A.4.9 Configuration buttons Bracket for vertical mounting of transmitter on 2-in. Rosemount 2051 requires option D4 (analog zero and pipe span), DZ (digital trim), M4 (LOI) for local configuration Carbon steel construction with carbon steel bolts ...
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB A.5 Dimensional drawings Figure A-1. Rosemount 2051C Exploded View A. Cover I. Sensor module B. Cover O-ring J. Process O-ring C. Terminal block K. Flange adapter O-ring D. Electronics housing L.
Page 85
A. Fieldbus display cover C. Transmitter circuitry B. HART display cover D. Terminal connections Dimensions are in inches (millimeters). Figure A-3. Rosemount 2051 Wireless Housing with Coplanar Platform 5.49 (139) 4.20 (107) 7.41 (188) Dimensions are in inches (millimeters). Figure A-4. Rosemount 2051C Coplanar with Rosemount 305 Three-Valve Coplanar Integral Manifold 5.66 (144)
Page 86
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Figure A-5. Coplanar Flange Mounting Configurations with Optional Bracket (B4) for 2-in. Pipe or Panel Mounting Panel mounting Pipe mounting 2.82 4.36 (72) (111) 2.18 (55) 7.03 (178) 6.25 (159) 6.15 2.8 (71) 3.51...
Page 87
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Figure A-7. Rosemount 2051C Coplanar with Rosemount 305 Three-Valve Traditional Integral Manifold 5.66 (144) 5.20 (132) 3.85 (98) 4.36 (111) 6.19 (157) 1.626 (41,3) 3.75 (95) max open 2.126 (54) 2.70 (69) 6.20 (158)
Page 88
A. Fieldbus display cover C. Transmitter circuitry B. HART display cover D. Terminal connections Dimensions are in inches (millimeters). Figure A-10. Rosemount 2051 Wireless Housing with In-line Platform 5.49 (139,3) 4.20 (106,6) 7.56 (192,1) A. U-Bolt bracket –14 NPT female or G A DIN 16288 make process connection Dimensions are in inches (millimeters).
Page 89
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Figure A-11. Rosemount 2051T with Rosemount 306 Two-Valve Integral Manifold 5.66 (144) 3.85 (98) 5.20 (132) 4.36 (111) 7.19 (182,7) 4.85 (123) 4.40 (112) 6.25 (159) max open A. Fieldbus display cover C.
Page 90
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Figure A-13. Rosemount 2051CFA Pak-Lok Annubar Flowmeter Front view Side view Top view Table A-10. Rosemount 2051CFA Pak-Lok Annubar Flowmeter Dimensional Data Sensor size A (max) B (max) C (max) D (max) 8.50 (215.9) 14.55 (369.6)
Page 91
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Figure A-14. Rosemount 2051CFC Compact Orifice Flowmeter Orifice plate side view Orifice plate front view Orifice plate top view 1.125 (28,58) 1.125 (28,58) Table A-11. Rosemount 2051CFC Dimensional Data Primary Transmitter element type...
Page 92
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Figure A-15. Rosemount 2051CFP Integral Orifice Flowmeter Side view Bottom view Front view 8.8 (223,46) 10.2 (258,28) (156,51) B.D. (134,51) Downstream Upstream Dimensions are in inches (millimeters). Table A-12. Rosemount 2051CFP Dimensional Data Line size Dimension -in.
Page 93
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Figure A-16. Rosemount 2051L Liquid Level 2-in. flange configuration 3- and 4-in. flange configuration (flush mount only) 3.85 (98) 3.85 (98) Optional flushing connection ring 5.66 (144) (lower housing) 5.20 (132) 4.36 (111) 6.60...
Page 94
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-13. 2051L Dimensional Specifications Flange Bolt circle Outside Pipe No. of Bolt hole Extension thickness diameter diameter Class size bolts diameter diameter 2 (51) 0.69 (18) 4.75 (121) 6.0 (152) 0.75 (19) ASME B16.5 (ANSI) 150...
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB A.6 Ordering information Table A-14. Rosemount 2051C Coplanar Pressure Transmitters Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time.
Page 96
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-14. Rosemount 2051C Coplanar Pressure Transmitters Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. Sensor fill fluid ★...
Page 97
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-14. Rosemount 2051C Coplanar Pressure Transmitters Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. ★...
Page 98
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-14. Rosemount 2051C Coplanar Pressure Transmitters Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. ★...
Page 99
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-14. Rosemount 2051C Coplanar Pressure Transmitters Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. Bolting materials ★...
Page 100
2051C D 2 A 2 2 A 1 A B4 M5 HART Revision 5 is the default HART output. The Rosemount 2051 with Selectable HART can be factory or field configured to HART Revision 7. To order HART Revision 7 factory configured, add option code HR7.
Page 101
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Transmitter conduit entry will be NPT and a NPT to G thread adapter will be provided. Configures the HART output to HART Revision 5. The device can be field configured to HART Revision 7 if needed. Configures the HART output to HART Revision 7.
Page 102
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-15. Rosemount 2051T In-line Pressure Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. Model Transmitter type ★...
Page 103
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-15. Rosemount 2051T In-line Pressure Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. ★...
Page 104
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-15. Rosemount 2051T In-line Pressure Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. ★...
Page 105
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-15. Rosemount 2051T In-line Pressure Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. Display and interface options ★...
Page 106
(c ode P). HART Revision 5 is the default HART output. The Rosemount 2051 with Selectable HART can be factory or field configured to HART Revision 7. To order HART Revision 7 factory configured, add option code HR7.
Page 107
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB 19. Available with 4–20 mA HART output code A, wireless output code X, F Fieldbus output code F, Rosemount 2051C Ranges 2–5 or OUNDATION Rosemount 2051T Ranges 1–4, SST and Alloy C 276 diaphragms and silicone fill fluid. High performance option includes 0.05% reference accuracy, and five year stability.
Page 108
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-16. Rosemount 2051CFA Annubar Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. Model Product description 2051CFA...
Page 109
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-16. Rosemount 2051CFA Annubar Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. Piping orientation ★...
Page 110
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-16. Rosemount 2051CFA Annubar Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. ★...
Page 111
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-16. Rosemount 2051CFA Annubar Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. Options (include with selected model number) Extended product warranty...
Page 112
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-16. Rosemount 2051CFA Annubar Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. OS&Y gate valve, carbon steel OS&Y gate valve, Alloy C-276 Special shipment...
Page 113
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-16. Rosemount 2051CFA Annubar Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. Sensor fill fluid and O-ring options ★...
Page 114
(page 85). HART Revision 5 is the default HART output. The Rosemount 2051 with Selectable HART can be factory or field configured to HART Revision 7. To order HART Revision 7 factory configured, add option code HR7. Not available with low power output code M.
Page 115
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-17. Rosemount 2051CFC Compact Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. Model Product description 2051CFC...
Page 116
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-17. Rosemount 2051CFC Compact Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. Differential pressure range ★...
Page 117
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-17. Rosemount 2051CFC Compact Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. ★...
Page 118
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-17. Rosemount 2051CFC Compact Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. (7)(12) Materials conformance NACE MR-0175/ISO 15156...
Page 119
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-17. Rosemount 2051CFC Compact Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. Sensor fill fluid and O-ring options ★...
Page 120
November 2016 00809-0300-4101, Rev BB HART Revision 5 is the default HART output. The Rosemount 2051 with Selectable HART can be factory or field configured to HART Revision 7. To order HART Revision 7 factory configured, add option code HR7.
Page 121
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-18. Rosemount 2051CFP Integral Orifice Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. Model Product description 2051CFP...
Page 122
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-18. Rosemount 2051CFP Integral Orifice Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. ★...
Page 123
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-18. Rosemount 2051CFP Integral Orifice Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. Transmitter housing material Conduit entry size ★...
Page 124
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-18. Rosemount 2051CFP Integral Orifice Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. (3)(8) Flow calibration Discharge coefficient verification...
Page 125
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-18. Rosemount 2051CFP Integral Orifice Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. ★...
Page 126
To improve pipe perpendicularity for gasket sealing, socket diameter is smaller than standard pipe O.D. HART Revision 5 is the default HART output. The Rosemount 2051 with Selectable HART can be factory or field configured to HART Revision 7. To order HART Revision 7 factory configured, add option code HR7.
Page 127
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-19. Rosemount 2051L Liquid Level Transmitter Ordering Information ★ ★ The Standard offering represents the most common options. The starred options ( ) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time.
Page 128
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-19. Rosemount 2051L Liquid Level Transmitter Ordering Information ★ ★ The Standard offering represents the most common options. The starred options ( ) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time.
Page 129
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-19. Rosemount 2051L Liquid Level Transmitter Ordering Information ★ ★ The Standard offering represents the most common options. The starred options ( ) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time.
Page 130
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-19. Rosemount 2051L Liquid Level Transmitter Ordering Information ★ ★ The Standard offering represents the most common options. The starred options ( ) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time.
Page 131
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-19. Rosemount 2051L Liquid Level Transmitter Ordering Information ★ ★ The Standard offering represents the most common options. The starred options ( ) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time.
Page 132
Typical model number: 2051L 2 A A0 X D 21 A A B4 M5 F1 HART Revision 5 is the default HART output. The Rosemount 2051 with Selectable HART can be factory or field configured to HART Revision 7. To order HART Revision 7 factory configured, add option code HR7.
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB A.7 Range limits Table A-20. Rosemount 2051C Differential/Gage Pressure Transmitter Range Limits Range 1 span Range 2 span Range 3 span Range 4 span Range 5 span Units 1000 83.040 8304 553.60...
Page 134
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Table A-22. Rosemount 2051T Gage and Absolute Pressure Transmitter Range Limits Range 1 span Range 2 span Range 3 span Range 4 span Range 5 span Units 8.30397 831.889 41.5198 4159.45 221.439 22143.9...
00809-0300-4101, Rev BB A.8 Profibus electronics spare parts ordering information Model Spare Part Type SP2051 Rosemount 2051 Electronics Board Spare Parts Transmitter Output Profibus — PA Protocol Options (include with existing model number) Configure Electronics for Configuration Buttons Configure Electronics for Local Operator Interface...
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB A.9 Other spare parts Terminal block Part number Standard terminal block assembly 02051-9005-0021 Transient terminal block assembly (option T1) 02051-9005-0022 FISCO terminal block assembly 02051-9005-0023 Part number LCD display LCD display kit PROFIBUS PA - Aluminum 03031-0193-0104...
Page 137
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Part number Flange/adapter bolt kit (73 mm [2.88 in.]) (set of 4) Carbon steel 03031-0306-0001 316 SST 03031-0306-0002 ASTM A 193, Grade B7M 03031-0306-0003 Part number Manifold/flange kit (57 mm [2.25 in]) (set of 4) Carbon steel 03031-0311-0001 316 SST...
Page 138
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB 316 SST 03031-0388-0022 Cast C-276 03031-0388-0023 Part number Gage coplanar flange Nickel-plated carbon steel 03031-0388-1025 316 SST 03031-0388-1022 Cast C-276 03031-0388-1023 Coplanar Flange Alignment Screw (package of 12) 03031-0309-0001 Part number Traditional flange 316 SST...
Page 139
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Part number Rosemount 2051T bracket kit B4 bracket, SST, 2-in. pipe mount, CS bolts 03031-0189-0004 Part number Rosemount 2051C Traditional flange bracket kits B1 bracket, 2-in. pipe mount, CS bolts 03031-0313-0001 B2 bracket, panel mount, CS bolts 03031-0313-0002...
Page 140
Specifications and Reference Data Reference Manual November 2016 00809-0300-4101, Rev BB Figure A-17. Spare Parts Diagram A. Electronics housing G. Electronics housing cover O-ring B. Terminal block H. Electronics board C. Electronics housing module O-ring I. Sensor module D. Process O-ring J.
Product Certifications Reference Manual November 2016 00809-0300-4101, Rev BB Canada Explosion-Proof, Dust Ignition Proof Special Conditions for Safe Use (X): Certificate: 2041384 1. Appropriate cable, glands and plugs need to be Standards: CAN/CSA C22.2 No. 0-10, suitable for a temperature of 5 °C greater than CSA Std C22.2 No.
Product Certifications Reference Manual November 2016 00809-0300-4101, Rev BB Markings: Ex db IIC T6... T4 Ga/Gb ≤ ≤ T6(–60 °C +70 °C), Table B-3. Input Parameters ≤ ≤ T4/T5(–60 °C +80 °C) FISCO Parameter Table B-4. Process Connection Temperature Voltage U 17.5 V Temperature Process...
Product Certifications Reference Manual November 2016 00809-0300-4101, Rev BB Special Condition for Safe Use (X): IECEx Type n Certificate: IECExBAS08.0046X 1. If the equipment is fitted with an optional 90 V Standards: IEC60079-0:2011, IEC60079-15:2010 transient suppressor, it is incapable of withstanding ≤...
Product Certifications Reference Manual November 2016 00809-0300-4101, Rev BB Special Conditions for Safe Use (X): Special Conditions for Safe Use (X): 1. If the equipment is fitted with an optional 90 V 1. Symbol “X” is used to denote specific conditions of transient suppressor, it is incapable of withstanding use: the 500 V insulation from earth test and this must be...
Product Certifications Reference Manual November 2016 00809-0300-4101, Rev BB B.8 Japan The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from Japan Flameproof impact or abrasion if located in Zone 0. Certificate: TC20598, TC20599, TC20602, TC20603 [HART];...
Product Certifications Reference Manual November 2016 00809-0300-4101, Rev BB B.11 Additional Certifications SBS American Bureau of Shipping (ABS) Type Approval Certificate: 09-HS446883B-3-PDA Intended Use: Marine and Offshore Applications Measurement of either Gauge or Absolute Pressure for Liquid, Gas, and Vapor ABS Rules: 2013 Steel Vessels Rules 1-1-4/7.7, 1-1-Appendix 3, 4-8-3/1.7, 4-8-3/13.1 SBV Bureau Veritas (BV) Type Approval...
Reference Manual Local Operator Interface (LOI) Menu 00809-0300-4101, Rev BB November 2016 Appendix C Local Operator Interface (LOI) Menu Overview ............. . . page 161 Detailed LOI Menu .
Page 172
Reference Manual Local Operator Interface (LOI) Menu 00809-0300-4101, Rev BB November 2016 Figure C-1. Detailed LOI Menu Either button Password protection is default out of the factory as off. The customer will need a configuration tool to set it. PASSWORD CODE FALSE CORRECT?
Page 173
Reference Manual Local Operator Interface (LOI) Menu 00809-0300-4101, Rev BB November 2016 Level Units Pressure Units Flow Units Cubic Meters Per Second Inches of water Percentage Chosen Volume Millimeters millibar Kilograms Per Minute Chosen Volume Centimeters Ton Per Hour Chosen Volume Pounds per square Meters...
Page 174
Reference Manual Local Operator Interface (LOI) Menu 00809-0300-4101, Rev BB November 2016 Local Operator Interface (LOI) Menu...
Reference Manual PROFIBUS® PA Block Information 00809-0300-4101, Rev BB November 2016 ® Appendix D PROFIBUS PA Block Information Overview ............. . . page 165 Safety messages .
Reference Manual PROFIBUS® PA Block Information 00809-0300-4101, Rev BB November 2016 PROFIBUS block parameters Table D-1 through Table D-5 can be used to cross reference parameters from the PROFIBUS specification, Class 2 Master, and Local Operator Interface (LOI). Table D-1. Physical Block Parameters ™...
Page 177
Reference Manual PROFIBUS® PA Block Information 00809-0300-4101, Rev BB November 2016 Table D-1. Physical Block Parameters ™ Index Parameter name name Definition location User-definable text to describe the DESCRIPTOR Descriptor device. User-definable message to the device or DEVICE_MESSAGE Message application in plant. Installation DEVICE_INSTAL_DATE Date of installation of the device.
Page 178
Reference Manual PROFIBUS® PA Block Information 00809-0300-4101, Rev BB November 2016 Table D-2. Transducer Block Parameters Index Parameter name DTM name Definition location The identification number of the plant ALERT_KEY Alert Key unit. This information may be used in the host for sorting alarms, etc. Contains desired mode of the block TARGET_MODE Target Mode...
Page 179
Reference Manual PROFIBUS® PA Block Information 00809-0300-4101, Rev BB November 2016 Table D-2. Transducer Block Parameters Index Parameter name DTM name Definition location Process PROCESS_CONNECTION_MATERIAL Connection Type of material of the flange Material Sensor temperature, in TEMPERATURE Temperature TEMPERATURE_UNIT Temperature Engineering units of the sensor TEMPERATURE_UNIT UNITS...
Page 180
Reference Manual PROFIBUS® PA Block Information 00809-0300-4101, Rev BB November 2016 Table D-3. Analog Input Block Parameters Index Parameter name DTM name Definition location Contains desired mode of the block TARGET_MODE Target Mode normally set by the operator or a control specification.
If blank, parameter is not applicable to LOI. Condensed status The Rosemount 2051 device utilizes condensed status as recommended by the Profile 3.02 specification and NE 107. Condensed status has some additional bits and changed bit assignments from classic status. Confirm bit assignment using...
Page 182
Reference Manual PROFIBUS® PA Block Information 00809-0300-4101, Rev BB November 2016 PROFIBUS® PA Block Information...
Page 183
Reference Manual Index 00809-0300-4101, Rev BB November 2016 .....18 Environmental considerations Approval Drawings ..151 Canadian Standards Association .
Page 184
Reference Manual Index 00809-0300-4101, Rev BA November 2016 Mounting Sensor ....... 18 Installation Module .
Page 186
Singapore 128461 Standard Terms and Conditions of Sale can be found at: +65 6777 8211 www.Emerson.com/en-us/pages/Terms-of-Use The Emerson logo is a trademark and service mark of Emerson Electric Co. +65 6777 0947 Annubar, Coplanar, Instrument Toolkit, PlantWeb, Rosemount, and Enquiries@AP.EmersonProcess.com Rosemount logotype are trademarks of Emerson Process Management.