Quick Start Guide
00825-0200-4101, Rev FC
September 2016
Rosemount™ 2051 Pressure Transmitter
Rosemount 2051CF Series Flowmeter
with F
Fieldbus Protocol
OUNDATION
Note
Before installing the transmitter, confirm the correct device driver is loaded on the host systems.
See
"System readiness" on page
3.

Advertisement

Table of Contents
loading

Summary of Contents for Emerson Rosemount 2051

  • Page 1 Quick Start Guide 00825-0200-4101, Rev FC September 2016 Rosemount™ 2051 Pressure Transmitter Rosemount 2051CF Series Flowmeter ™ with F Fieldbus Protocol OUNDATION Note Before installing the transmitter, confirm the correct device driver is loaded on the host systems. “System readiness” on page...
  • Page 2: Table Of Contents

    September 2016 Quick Start Guide NOTICE This guide provides basic guidelines for Rosemount 2051 Transmitters. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-Proof, Flame-Proof, or intrinsically safe (I.S.) installations. Refer to the Rosemount 2051 Reference Manual for more instruction.
  • Page 3: System Readiness

    Download the correct device driver at your host vendor download site,  EmersonProcess.com or Fieldbus.org. Rosemount 2051 device revisions and drivers Table 1 provides the information necessary to ensure you have the correct device driver and documentation for your device.
  • Page 4: Mount The Transmitter

    September 2016 Quick Start Guide 2.0 Mount the transmitter 2.1 Liquid applications Coplanar In-line 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so the drain/vent valves are oriented upward.
  • Page 5 Quick Start Guide September 2016 Figure 2. Panel and Pipe Mounting Panel mount Pipe mount Coplanar flange Traditional flange Rosemount 2051T panel bolts are customer supplied.
  • Page 6 Use only bolts supplied ™ with the transmitter or sold by Emerson as spare parts. Figure 3 on page 6 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly.
  • Page 7 Quick Start Guide September 2016 Table 2. Torque Values for the Flange and Flange Adapter Bolts Bolt material Head markings Initial torque Final torque Carbon Steel (CS) 300 in-lb 650 in-lb Stainless Steel (SST) 150 in-lb 300 in-lb 2.5 O-rings with flange adapters Failure to install proper flange adapter O-rings may cause process leaks, which can result in death or serious injury.
  • Page 8: Tagging

    September 2016 Quick Start Guide Keep the vent path free of any obstruction, including but not limited to paint, dust, and lubrication by mounting the transmitter so fluids can drain away. Figure 4. In-line Gage Low Side Pressure Port A. Pressure port location 3.0 Tagging 3.1 Commissioning (paper) tag To identify which device is at a particular location use the removable tag provided...
  • Page 9: Housing Rotation

    Quick Start Guide September 2016 Note The device description loaded in the host system must be at the same revision as this device. The device description can be downloaded from the host system website or EmersonProcess.com/Rosemount by selecting Download Device Drivers under Product Quick Links.
  • Page 10: Wire, Ground, And Power Up

    September 2016 Quick Start Guide Note It is recommended the cover be tightened until there is no gap between the cover and housing. Figure 7. Simulate and Security Switches A. Simulate disabled position D. Security locked position B. Simulate switch E.
  • Page 11: Power Supply

    September 2016 Note The Rosemount 2051 power terminals are polarity insensitive, which means the electrical polarity of the power leads does not matter when connecting to the power terminals. If polarity sensitive devices are connected to the segment, terminal polarity should be followed.
  • Page 12 September 2016 Quick Start Guide 6.3 Power conditioner A Fieldbus segment requires a power conditioner to isolate the power supply, filter, and decouple the segment from other segments attached to the same power supply. 6.4 Grounding Signal wiring of the Fieldbus segment can not be grounded. Grounding out one of the signal wires will shut down the entire Fieldbus segment.
  • Page 13: Configure

    DD methods for configuration and to display data consistently across platforms. There is no requirement that a host or configuration tool support these features. Use the following block examples to do basic configuration to the transmitter. For more advanced configurations, see the Rosemount 2051 Reference Manual.
  • Page 14: Before You Begin

    September 2016 Quick Start Guide Figure 10. Basic Configuration Menu Tree (Calibration) (Overview ) Primary Value Pressure Sensor Trim Calibration Sensor Limits Device Information Restore Factory Calibration Locate Device Last Calibration Points Scale Gauges Calibration Details (Device Information ) (Materials of Construction ) Identification (1) Sensor Revisions...
  • Page 15 Quick Start Guide September 2016 3. To disable the software write lock: a. Navigation: from the Overview screen, select Device Information and then select the Security and Simulation tab. b. Perform “Write Lock Setup” to disable software write lock. c. Place the control loop in “Manual” mode before beginning AI block configuration Note...
  • Page 16 September 2016 Quick Start Guide 3. To select the signal conditioning “L_TYPE” from the drop down menu: a. Select L_TYPE: “Direct” for pressure measurements using the device default units. b. Select L_TYPE: “Indirect” for other pressure or level units. c. Select L_TYPE: “Indirect Square Root” for flow units. 4.
  • Page 17 Quick Start Guide September 2016 Note Guided setup will automatically go through each step in the proper order. Check the box next to each parameter to be displayed to a maximum of  four parameters. The LCD display will continuously scroll through the selected parameters.
  • Page 18 September 2016 Quick Start Guide 7.5 AI block configuration parameters Use the Pressure, DP Flow, and DP Level examples for guides. Parameters Enter data Channel 1 = Pressure, 2 = Sensor Temp L-Type Direct, Indirect, or Square Root XD_Scale Scale and Engineering Units torr @ 0 °C O @ 4 °C O @ 4 °C...
  • Page 19: Zero Trim The Transmitter

    Quick Start Guide September 2016 DP Level example Parameters Enter data Channel L_Type Indirect XD_Scale 0–300 inH O @ 68 °F Note Select only the units that are supported by the device. Out_Scale 0–25 ft 7.6 Display pressure on the LCD display meter Select the Pressure check box on the display configuration screen.
  • Page 20: Product Certifications

    ≤ +70 °C); Type 4x Special Condition for Safe Use (X): 1. The Rosemount 2051 Transmitter housing contains aluminum and is considered a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact and friction.
  • Page 21 Quick Start Guide September 2016 E6 Canada Explosion-Proof, Dust Ignition Proof Certificate: 2041384 Standards: CAN/CSA C22.2 No. 0-10, CSA Std C22.2 No. 25-1966, CSA Std C22.2 No. 30-M1986, CAN/CSA-C22.2 No. 94-M91, CSA Std C22.2 No.142-M1987, CAN/CSA-C22.2 No.157-92, CSA Std C22.2 No. 213-M1987, CAN/CSA-E60079-0:07, CAN/CSA-E60079-1:07, CAN/CSA-E60079-11-02, CAN/CSA-C22.2 No.
  • Page 22 September 2016 Quick Start Guide Special Conditions for Safe Use (X): 1. If the equipment is fitted with an optional 90 V transient suppressor, it is incapable of withstanding the 500 V isolation from earth test and this must be taken into account during installation.
  • Page 23 Quick Start Guide September 2016 9.5 International E7 IECEx Flameproof Certificate: IECExKEM08.0024X Standards: IEC60079-0:2004, IEC60079-1:2007-04, IEC60079-26:2006 Markings: Ex d IIC T6/T5 IP66, T6(–50 °C ≤ T ≤ +65 °C), T5(–50 °C ≤ T ≤ +80 °C) Table 5. Process Temperature Temperature class Process temperature –50 °C to +65 °C...
  • Page 24 September 2016 Quick Start Guide IG IECEx FISCO Certificate: IECExBAS08.0045X Standards: IEC60079-0:2011, IEC60079-11:2011 Markings: Ex ia IIC T4 Ga (–60 °C ≤ T ≤ +60 °C) Table 7. Input Parameters Parameter FISCO Voltage U 17.5 V Current I 380 mA Power P 5.32 W Capacitance C...
  • Page 25 Quick Start Guide September 2016 I2 INMETRO Intrinsic Safety Certificate: UL-BR 14.0759X Standards: ABNT NBR IEC 60079-0:2008 + Errata 1:2011; ABNT NBR IEC 60079-11:2009 Markings: Ex ia IIC T4 Ga (–60 °C ≤ T ≤ +70 °C) Table 8. Input Parameters Parameter HART Fieldbus/PROFIBUS...
  • Page 26 September 2016 Quick Start Guide 9.7 China E3 China Flameproof Certificate: GYJ13.1386X; GYJ15.1366X [Flowmeters] Standards: GB3836.1-2010, GB3836.2-2010, GB3836.20-2010-2010 Markings: Pressure Transmitter: Ex d IIC Gb, T6(–50 °C ≤ T ≤ +65 °C), T5(–50 °C ≤ T ≤ +80 °C) Flowmeter: Ex d IIC Ga/Gb, T6(–50 °C ≤ T ≤...
  • Page 27 Quick Start Guide September 2016 3. Intrinsically Safe parameters: Parameter HART Fieldbus/PROFIBUS Voltage U 30 V 30 V Current I 200 mA 300 mA Power P 1.3 W Capacitance C 0.012 μF 0 μF Inductance L 0 mH 0 mH Note 1: FISCO parameters comply with the requirements for FISCO field devices in GB3836.19-2010.
  • Page 28 September 2016 Quick Start Guide 9.10 Combinations K1 Combination of E1, I1, N1, and ND K2 Combination of E2 and I2 K5 Combination of E5 and I5 K6 Combination of E6 and I6 K7 Combination of E7, I7, N7, and IECEx Dust IECEx Dust Certificate: IECEx BAS 08.0058X Standards: IEC60079-0:2011, IEC60079-31:2008...
  • Page 29 Quick Start Guide September 2016 Figure 11. Rosemount 2051 EC Declaration of Conformity...
  • Page 30 September 2016 Quick Start Guide...
  • Page 31 Quick Start Guide September 2016...
  • Page 32 September 2016 Quick Start Guide...
  • Page 33 Quick Start Guide September 2016 Rosemount 2051 China RoHS List of Rosemount 2051 Parts with China RoHS Concentration above MCVs / Hazardous Substances Hexavalent Polybrominated Polybrominated Part Name Lead Mercury Cadmium Chromium biphenyls diphenyl ethers (Pb) (Hg) (Cd) (Cr +6)
  • Page 34 +65 6777 8211 Standard Terms and Conditions of Sale can be found at www.Emerson.com/en-us/pages/Terms-of-Use.aspx +65 6777 0947 The Emerson logo is a trademark and service mark of Emerson Enquiries@AP.EmersonProcess.com Electric Co. DeltaV, Rosemount, and Rosemount logotype are trademarks of Middle East and Africa Regional Office Emerson Process Management.

This manual is also suitable for:

Rosemount 2051cf series

Table of Contents