Level Configuration - Emerson Rosemount 2051 Reference Manual

Pressure transmitter with profibus pa protocol
Hide thumbs Also See for Rosemount 2051:
Table of Contents

Advertisement

Reference Manual
00809-0300-4101, Rev BB
1. From the Basic Setup >> Units >> Primary Value >> Primary Value Type dropdown menu,
select pressure.
2. Select Units.
Note
Pressure units in steps 2a, 2b, and
a. From the Basic Setup >> Units >> Primary Value >> Scale In (Transducer Block) >> Unit
b. From the Basic Setup >> Units >> Primary Value >> Unit (PV) dropdown, select
c. From the Basic Setup >> Units >> Output Signal (Analog Input Block) >> Unit (Out Scale)
3. Enter scaling.
Note
Scaling is done in the Transducer Block. No scaling required for pressure measurement.
a. In the Basic Setup >> Units >> Primary Value >> Scale In (Transducer Block) field,
b. In the Basic Setup >> Units >> Primary Value >> Scale Out (Transducer Block) field,
4. Verify Analog Input (AI) Block.
Note
Scaling should not be repeated in the Analog Input Block. To ensure no additional scaling is
being done on the Al Block, set the lower values in steps
to 100.
a. In the Basic Setup >> Units >> Process Value Scale (Analog Input Block) field, enter upper
b. In the Basic Setup >> Units >> Output Signal (Analog Input Block) field, enter upper and
c. From the Basic Setup >> Units >> Output Signal (Analog Input Block) >> Linearization
2.6.3

Level configuration

LOI
To configure the Rosemount 2051 for Level measurement with the LOI, select UNITS >>
LEVEL. When configuring level units, the following parameters are set:
Measurement type: Level
Linearization (Transducer Block): None
During unit configuration, the user defines scaling and units per the application
requirements. See
further scaling help.
Configuration
(Secondary Value 1) dropdown, select engineering unit.
engineering unit.
dropdown, select engineering unit.
enter upper and lower values (this value should correspond to the unit selected in
step 2a).
enter upper and lower values (this value should correspond to the unit selected in
step 2b).
and lower values (this value should correspond to the unit selected in step 2b).
lower values (this value should correspond to the unit selected in step 2c).
Type dropdown, select Square Root.
Appendix C: Local Operator Interface (LOI) Menu
2c
must match.
4a
Configuration
November 2016
and
4b
to 0 and the upper values
for detailed menu for
11