C-2-2: Fx 2N -4Ad Extension Configuration (Motorola Format - Mitsubishi FX2N-32DP-IF User Manual

Melsec fx series
Hide thumbs Also See for FX2N-32DP-IF:
Table of Contents

Advertisement

FX2N-32DP-IF Profibus-DP Interface Unit
C-2-2:
FX
-4AD Extension Configuration (Motorola Format)
2N
Requirements:
• Cyclic data is 4 word inputs in every cycle.
Table C-5:
1st
2nd
3rd
4th
• Parameter is 41 bytes.
Table C-6:
Nr.
Parameter Name
00
Channel 1 input
(1st)
01
Channel 2 input
(2nd)
02
Channel 3 input
(3rd)
03
Channel 4 input
(4th)
04
Next parameter
(5th)
uses EEPROM.
05
..O/G setting
(6th)
prohibit/permit
RESET/INIT.
06
MODULE TO
(7th)
DEFAULT
VERIFY RESET/
*1
07
INITIALISE
(8th)
COMMAND
*2
08
A/D conversion
(9th)
speed
09
Next parameter
(10th)
uses EEPROM.
Cyclic Data of FX
(Motorola Format)
Send Data
None
FX
-4AD Extension Configuration (Motorola Format)
2N
direct input value ch1
averaged input value ch1
direct input value ch2
averaged input value ch2
direct input value ch3
averaged input value ch3
direct input value ch4
averaged input value ch4
DON'T write parameter to
EEPROM
write parameter to EEPROM
permit offset/gain setting
prohibit offset/gain setting
no reset/initialisation
RESET/INITIALISE MODULE
no reset/initialisation
RESET/INITIALISE MODULE
normal speed (15ms/ch)
high speed (6ms/ch)
DON'T write parameter to
EEPROM
write parameter to EEPROM
-4AD Extension Configuration
2N
Choose between direct and averaged value ch1
Choose between direct and averaged value ch2
Choose between direct and averaged value ch3
Choose between direct and averaged value ch4
Value Setting List
Receive Data
Description
Select input value type for channel 1
from the available options (BFM #9 or
BFM #5).
Select input value type for channel 2
from the available options (BFM #10
or BFM #6).
Select input value type for channel 3
from the available options (BFM #11
or BFM #7).
Select input value type for channel 4
from the available options (BFM #12
or BFM #8).
The 6th parameter uses EEPROM.
Select "writing to EEPROM" setting
from the available options.
Select prohibit/permit setting of offset/
gain from the available options (BFM
#21).
Select initialize module setting from
the available options (BFM #20).
Select initialize module setting from
the available options (BFM #20).
Select conversion speed from the
available options (BFM #15).
The 11th ~13th parameter use
EEPROM. Select "writing to
EEPROM" setting from the available
options.