FX2N-32DP-IF Profibus-DP Interface Unit
7.3

Configuring Slave Parameter

Caution:
The user parameter data and configuration of the 32DP-IF must always be consistent. To
ensure that the user parameter data and the configuration of the 32DP-IF are matching
each other, the user parameter data set should always be constructed by using the GSD file
that has been delivered with the 32DP-IF.
7.3.1

Configuring Slave Parameter by GSD file

The parameter setting of the 32DP-IF can be entirely defined using the GSD file that comes on
the disk together with 32DP-IF. For an easy adjustment of all user parameter data, the
MELSOFT GX-Configurator-DP (or Mitsubishi ProfiMap Software V2.x or later) (hereafter
called "GX-Configurator-DP") or a configuration software from another vendor which is
supporting extended parameter setting should be used.
For example configuring slave parameter with ProfiMap, refer to appendix A and C.
For example configuring slave parameter with GX-Configurator-DP , refer to appendix B and C.
Note:
In configuring 32DP-IF GSD file, first assign special function blocks, second extension I/O
units/blocks input data, and finally extension I/O units/blocks output data. The physical
placement of the modules does not have to correspond with the GSD file order. However,
the special function blocks must be configured in the same order as they are connected
physically to the unit.