Specifications; General Specifications - Mitsubishi FX2N-32DP-IF User Manual

Melsec fx series
Hide thumbs Also See for FX2N-32DP-IF:
Table of Contents

Advertisement

FX2N-32DP-IF Profibus-DP Interface Unit
4.

Specifications

4.1

General Specifications

Table 4.1: General Specifications
Operating Temperature
Storage Temperature
Operating Humidity
Storage Humidity
Vibration Resistance
- Direct Mounting
Vibration Resistance
- DIN rail Mounting
Shock Resistance
Noise Immunity
Dielectric
Withstand
Voltage
Insulation Resistance
Grounding
Complies with
Item
0 to 55 °C (32 to 131 °F)
-20 to 70 °C (-4 to 158 °F)
35 to 85% Relative Humidity, No condensation
35 to 90% Relative Humidity, No condensation
Conforms to EN68-2-6; 10 - 57 Hz: 0.075 mm Half Amplitude
Conforms to EN68-2-6; 10 - 57 Hz: 0.035 mm Half Amplitude
Conforms to EN68-2-27: 147m/s
1,000 Vp-p, 1microsecond, 30 - 100 Hz, tested by noise simulator
FX
-32DP-IF
2N
(AC Power
1,500 V AC > 1 min, tested between all points, terminals and ground
Supply Type)
FX
-32DP-IF-D
2N
(DC Power
500 V AC > 1 min, tested between all points, terminals and ground
Supply Type)
5 MΩ > at 500 V DC, tested between all points, terminals and ground
Grounding resistance is 100 Ω or less
UL508
Description
57 - 150 Hz: 9.8 m/s
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
57 - 150 Hz: 4.9 m/s
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
3 times in each direction X, Y, and Z
Specifications 4
2
Acceleration
2
Acceleration
2
Acceleration, Action Time: 11 ms
4-1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx2n-32dp-if-d

Table of Contents