FX2N-32DP-IF Profibus-DP Interface Unit
Table C-35: FX
Nr.
Parameter Name
00
Counter mode
(1st)
01
ring length lower
(2nd)
word
02
ring length upper
(3rd)
word
03
counter curr. value
(4th)
lower word
04
counter curr. value
(5th)
upper word
-1HC Short Configuration
2N
Value Setting List
2-ph. input 1 edge count 32 bit
2-ph. input 1 edge count 16 bit
2-ph. input 2 edge count 32 bit
2-ph. input 2 edge count 16 bit
2-ph. input 4 edge count 32 bit
2-ph. input 4 edge count 16 bit
1-ph. 2-input +/- pls. 32 bit
1-ph. 2-input +/- pls. 16 bit
1-ph. 1-inp. HW UP/DOWN 32 bit
1-ph. 1-inp. HW UP/DOWN 16 bit
1-ph. 1-inp. SW UP/DOWN 32 bit
1-ph. 1-inp. SW UP/DOWN 16 bit
Default: 0 (0000Hex)
Default: 1 (0001Hex)
Default: 0 (0000Hex)
Default: 0 (0000Hex)
Description
Select counter mode from the
available options. (BFM #0)
Set lower word value for ring length
(BFM #2)
Setting range (BFM #2, #3):
2 ~ 65535 (00002 ~ 10000Hex)
Set upper word value for ring length
(BFM #3)
Setting range (BFM #3, #2):
2 ~ 65535 (00002 ~ 10000Hex)
Set lower word for counter current
value. (BFM #20)
Setting range (BFM #21, #20):
-2,147,483,648 ~ +2,147,483,647
(00000000 ~ FFFFFFFFHex)
Set upper word for counter current
value. (BFM #21)
Setting range (BFM #21, #20):
-2,147,483,648 ~ +2,147,483,647
(00000000 ~ FFFFFFFFHex)