Mitsubishi FX2N-32DP-IF User Manual page 180

Melsec fx series
Hide thumbs Also See for FX2N-32DP-IF:
Table of Contents

Advertisement

FX2N-32DP-IF Profibus-DP Interface Unit
Table C-64: FX
Nr.
Parameter Name
17
Jog speed upper
(18th)
word
18
zero ret. hi. speed
(19th)
lower word
19
zero ret. hi. speed
(20th)
upper word
20
zero ret. creep
(21st)
speed
21
zero point signal
(22nd)
number
22
zero point address
(23rd)
lower word
23
zero point address
(24th)
upper word
-10PG 6W-IF (Intel Format)
2N
Value Setting List
Default: 0 (0000 Hex)
Default: 41248 (A120 Hex)
Default: 7 (0007 Hex)
Default: 1000 (03EB Hex)
Default: 1 (0001 Hex)
Default: 0 (0000 Hex)
Default: 0 (0000 Hex)
Description
Set lower word of JOG speed.
(BFM #4)
Setting range (BFM #4, #3):
-2,147,483,648 to 2,147,483,467
(00000000 to FFFFFFFF Hex)
The range of pulse-converted value
is 1 to 1,000,000 Hz (000000001 to
000F4240 Hex)
Set lower word of the home position
return speed. (BFM #5)
Setting range (BFM #6, #5):
1 to 2,147,483,467 (00000001 to
7FFFFFFF Hex)
The range of pulse-converted value
is 1 to 1,000,000 Hz (000000001 to
000F4240 Hex)
Set upper word of the home
position return speed. (BFM #6)
Setting range (BFM #6, #5):
1 to 2,147,483,467 (00000001 to
7FFFFFFF Hex)
The range of pulse-converted value
is 1 to 1,000,000 Hz (000000001 to
000F4240 Hex)
Set creep speed of home position
return. (BFM #7)
Setting range:
0 to 32767 (0000 to 7FFF Hex)
The range of pulse-converted value
is 0 to 30000 Hz (0000 to 7530
Hex)
Set number of zero point signal.
(BFM #8)
Setting range:
0 to 32767 (0000 to 7FFF Hex)
Set lower word of home position
address. (BFM #9)
Setting range (BFM #10, #9):
-2,147,483,648 to 2,147,483,467
(00000000 to FFFFFFFF Hex)
Set upper word of home position
address. (BFM #10)
Setting range (BFM #10, #9):
-2,147,483,648 to 2,147,483,467
(00000000 to FFFFFFFF Hex)
C-74
Appendix C:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx2n-32dp-if-d

Table of Contents