Mitsubishi FX2N-32DP-IF User Manual page 62

Melsec fx series
Hide thumbs Also See for FX2N-32DP-IF:
Table of Contents

Advertisement

FX2N-32DP-IF Profibus-DP Interface Unit
Table 5.14: Special Data Registers (D8060 ~ D8069)
Diagnostic
Device
8
(4)
D8060 (
)
8
(4)
D8061 (
)
D8062, D8063 Reserved
8
(4)
D8064 (
)
D8065,D8066
8
(4)
D8067 (
)
8
(4)
D8068 (
)
D8069
Error
Name
code
I/O configuration
This device contains the lowest device address that caused the
error
error. Check D8061
0
6102
32DP-IF
6103
hardware error
6129
0
6406
6407
Parameter error
6408
6410
Reserved
0
Operation error
6708
Parameter error
This device contains the lowest special function block's address
and operation
that caused the error. Check D8064 and D8067.
error
Reserved
No error
Operation circuit error: Please contact a service
representative.
I/O bus error: Check extension cable for Extension I/O
units/blocks.
BFM #29 (error status) of a connected special function
block shows a value that is different from "0". Please
check the diagnosis message at the DP-master.
No error
Parameter error for extension units/blocks: Check error
code in D8068, and parameter in the DP-master.
Parameter length error: Parameter data too long, check
parameter's length in the DP-master.
Configuration error for extension units/blocks: Check error
code in D8068, and parameter in the DP-master.
DIP switch error: DIP switch error refer to the address
setting DIP switch on the 32DP-IF module: DIP switch
position does not decided ON or OFF when the power of
32DP-IF is turned ON. Check position of DIP switch. If the
position of DIP switch is ON or OFF, please contact a
service representative.
No error
Operation error: Operation error for transmitting special
function block occurs, check error code in D8068, and
DP-master parameter, and extension cable.
Advanced Devices 5
Description
5-12

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx2n-32dp-if-d

Table of Contents